Trade Price
£1,313.30
Per
1
Unit
EA
Pack Quantity
1
This product is part of the Preventa XPS MP, XPS MC, XPS MCM range, an offer of safety controllers. This safety controller provides 16 inputs and 32 LEDs for signalling. It is a safety controller with a power consumption of 12W, control circuit voltage of 28.8V and a rated supply voltage of 24V DC. Supported communication port protocols are Modbus with RJ45 port, CANopen with 9-way SUB-D male port. It is an IP20 rated product. Its dimensions are 74mm (Width) x 153mm (Depth) x 151.5mm (Height). It weighs 0.82kg. It is designed to provide a solution for safety applications requiring conformity to Performance Level PL e/Category 4 EN/ISO 13849-1 and SIL3 EN/IEC 61508. This product is certified by UL, CSA and TUV. It meets EN 574/ISO 13851, EN 1760-1/ISO 13856-1, EN/IEC 61496-1, EN/IEC 60204-1, EN/IEC 60947-5-1, EN 954-1/EN/ISO 13849-1 and IEC 61508 standards. Simple, it features redundancy principle micro-processor based technology to provide advanced functions, flexibility regarding the choice of safety function and more precise diagnostics are just some of its advantages. Safety controller XPS MC is configured with a simple software environment where functions are mapped to the various controller outputs according to the application requirements.
Range of produc
Preventa Safety automation
Product or component type
Configurable safety controller
safety module name
XPSMC
Safety use category
Category 4 maximum conforming to EN 954-1/EN/ISO 13849-1 PLE maximum conforming to ISO 13849-1 SIL 3 maximum conforming to IEC 61508
Type of start
Configurable
Standards
IEC 61496-1 EN 574/ISO 13851 EN 1760-1/ISO 13856-1 IEC 61508 EN 954-1/EN/ISO 13849-1 IEC 60947-5-1 IEC 60204-1
product certifications
UL TÜV CSA
[Us] rated supply voltage
24 V DC - 20...20 %
Number of inputs
16
Communication port protocol
CANopen with 1 SUB-D 9-pin male port(s), serial link, transmission rate: 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800 kbps or 1 Mbps Modbus with 1 RJ45 port(s), serial link, transmission rate: 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps
Safety level
Can reach PL e/category 4 conforming to EN 954-1/EN/ISO 13849-1 Can reach SIL 3 conforming to IEC 61508
Function of module
Dynamic monitoring of hydraulic valves on linear presses Eccentric press Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring Enabling switch monitoring, 2 or 3 contacts Foot switch monitoring Guard monitoring for injection presses and blowing machines Guard monitoring with 1 or 2 limit switches Hydraulic press Magnetic switch monitoring category 4 conforming to EN/IEC 61496 Monitoring safety stop at top dead centre on eccentric press category 3 conforming to EN 574/ISO 13851 Muting function of light curtains Position selector Safety mat monitoring Safety time delays Shaft/chain breaking monitor Zero speed detection Light curtain monitoring category 4 conforming to IEC 61496 Two-hand control category 3 conforming to EN 574/ISO 13851
Synchronisation time between inputs
Depending on configuration selected
Power consumption in W
12 W
Input protection type
External fuse 16 A
[Uc] control circuit voltage
28.8 V
Maximum line resistance
100 Ohm <2000 m
Output type
2 relays, 2 NO contacts (4 NO total) circuit(s) Solid state, 6 circuit(s), volt-free
Breaking capacity
2 A at 24 V for static output circuit 1.5 A at 24 V (DC-13) time constant: 50 ms for relay output
Output thermal current
4 A for both outputs simultaneously 6 A for 1 output and 2 A for the other for relay output
[Ith] conventional free air thermal current
16 A for relay output 6.5 A for static output circuit
Associated fuse rating
16 A gL for power supply 4 A gL for relay output 6 A fast blow for relay output
Minimum output current
10 mA for relay output
Minimum output voltage
17 V for relay output
Response time
Configurable : 20 ms or 30 ms with software XPSMCWIN
[Ui] rated insulation voltage
300 V (pollution degree 2) conforming to IEC 60647-5-1, DIN VDE 0110 part 1
[Uimp] rated impulse withstand voltage
4 kV overvoltage category III conforming to IEC 60647-5-1, DIN VDE 0110 part 1
Method of access
Slave
Exchange size
14 words
Number of addresses
1…127 for CANopen 1…247 for Modbus
Parity
Even for Modbus No for Modbus Odd for Modbus
Data format
1 start bit/8 data bits 1 stop bit even or odd 2 stop bits without parity RTU (Remote Terminal Unit) mode
Supported modbus function
01: 8-bit output data/32-bit input data 02: 32-bit input data/8-bit output data 03: information and errors
Local signalling
32 LEDs
mounting support
Mounting plate
Depth
153 mm
height
151.5 mm
Width
74 mm
Net weight
0.82 kg
IP degree of protection
IP20 conforming to IEC 60529
ambient air temperature for operation
-10…55 °C
Ambient air temperature for storage
-25…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
9.500 cm
Package 1 Width
18.000 cm
Package 1 Length
26.000 cm
Package 1 Weight
1.265 kg
Unit Type of Package 2
S04
Number of Units in Package 2
6
Package 2 Height
30.000 cm
Package 2 Width
40.000 cm
Package 2 Length
60.000 cm
Package 2 Weight
8.459 kg
Warranty
18 months
Datasheet