Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Range of product
Modicon X80
Product or component type
Discrete I/O module
Product specific application
For severe environments
Discrete input number
8
input type
Current sink (logic positive)
Discrete input voltage
24 V DC, discrete input logic: positive
Discrete input current
3.5 mA
Discrete output number
8
Discrete output type
Relay
Discrete output voltage
24 V 19...30 V DC 24...240 V 19...264 V AC
discrete output current
2000 mA
Input compatibility
With 2-wire/3-wire proximity sensors conforming to IEC 60947-5-2 With 2-wire/3-wire proximity sensors conforming to IEC 61131-2 type 3
Sensor power supply
19...30 V 60 °C 21.1...29.0 V 70 °C
Current state 1 guaranteed
>= 2 mA
Current state 0 guaranteed
<= 1.5 mA
Input impedance
6800 Ohm
Insulation resistance
> 10 MOhm 500 V DC
Power dissipation in W
3.1 W
DC typical response time
4 ms
DC maximum response time
7 ms
Response time on output
<= 8 ms deactivation <= 10 ms activation
Paralleling of inputs
No
Typical current consumption
79 mA at 3.3 V DC
MTBF reliability
940000 H
Protection type
1 external fuse per group of input channel0.5 A fast blow reverse polarity protection on input 1 external fuse per output channel or group of output channel fast blow
Voltage detection threshold
< 14 V DC sensor fault > 18 V DC sensor OK
Minimum switching current
1 mA 5 V DC
Maximum switching voltage
125 V DC 264 V AC
Mechanical durability
20000000 cycles
Electrical durability
AC-14: 100000 cycles at 120 VA 240 V at 70 °C (load factor 0.7) AC-14: 100000 cycles at 150 VA 200 V at 70 °C (load factor 0.7) AC-14: 100000 cycles at 240 VA 240 V at -25…60 °C (load factor 0.7) AC-14: 100000 cycles at 300 VA 200 V at -25…60 °C (load factor 0.7) AC-15: 100000 cycles at 100 VA 200 V at 70 °C (load factor 0.35) AC-15: 100000 cycles at 120 VA 240 V at -25…60 °C (load factor 0.35) AC-15: 100000 cycles at 200 VA 200 V at -25…60 °C (load factor 0.35) AC-15: 100000 cycles at 60 VA 240 V at 70 °C (load factor 0.35) DC-13: 100000 cycles at 12 W 24 V at 70 °C DC-13: 100000 cycles at 24 W 24 V at -25…60 °C AC-14: 300000 cycles at 36 VA 240 V at 70 °C (load factor 0.7) AC-14: 300000 cycles at 40 VA 200 V at 70 °C (load factor 0.7) AC-14: 300000 cycles at 72 VA 240 V at -25…60 °C (load factor 0.7) AC-14: 300000 cycles at 80 VA 200 V at -25…60 °C (load factor 0.7) AC-15: 300000 cycles at 18 VA 240 V at 70 °C (load factor 0.35) AC-15: 300000 cycles at 30 VA 200 V at 70 °C (load factor 0.35) AC-15: 300000 cycles at 36 VA 240 V at -25…60 °C (load factor 0.35) AC-15: 300000 cycles at 60 VA 200 V at -25…60 °C (load factor 0.35) DC-13: 300000 cycles at 3.6 W 24 V at 70 °C DC-13: 300000 cycles at 7.2 W 24 V at -25…60 °C
Switching frequency
1 Hz
Status LED
1 LED (green) module operating (RUN) 1 LED per channel (green) channel diagnostic 1 LED (red) module error (ERR) 1 LED (red) module I/O
Net weight
0.135 kg
IP degree of protection
IP20
Directives
2014/35/EU - low voltage directive 2014/30/EU - electromagnetic compatibility
Environmental characteristic
Gas resistant class Gx Gas resistant class 3C4 Dust resistant class 3S4 Sand resistant class 3S4 Salt resistant level 2 Mold growth resistant class 3B2 Fungal spore resistant class 3B2
Dielectric strength
1500 V AC at 50/60 Hz 1 minute, primary/secondary 2830 V AC at 50/60 Hz 1 minute, output relay 500 V DC 1 minute, between group of I/O
Vibration resistance
3 gn
Shock resistance
30 gn
Ambient air temperature for storage
-40…85 °C
Ambient air temperature for operation
-25…70 °C
Relative humidity
5…95 % at 55 °C without condensation
Protective treatment
Conformal coating
Operating altitude
0...2000 m 2000...5000 m with derating factor
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.500 cm
Package 1 Width
11.000 cm
Package 1 Length
12.000 cm
Package 1 Weight
175.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
15
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
2.625 kg
Warranty
18 months
Datasheet
Product Catalogue