Trade Price
£1,552.57
Per
1
Unit
EA
Pack Quantity
1
TeSys GS fuse switch-disconnector, 3 poles (3P), 630A/1000V, to be used with type BS fuse links size C1-C2 up to 630A, for motor applications up to 355kW@400V AC-23. To be equipped with an external front side or right-hand side mounting operating handle GS2AH (several models available). Screw terminals to be equipped with upstream and downstream 3P terminal shrouds GS1AP73 (to be ordered separately), it provides high short circuit current rating 100kA@400V. Add-on auxiliary contact modules front mounting GS1AM (early-break and position signaling) can complete the assembly (to be ordered separately). Multi standards certified (IEC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys
Product name
TeSys GS
Device short name
GS2S
Product or component type
Switch-disconnector-fuse
Poles description
3P
Protected poles description
3t
Contacts type and composition
3 NO
[Ith] conventional free air thermal current
630 A (at 40 °C)
[Ie] rated operational current
400 A at 440 V 2 poles in series per phase and not juxtaposed DC-23A 630 A at 440 V 2 poles in series per phase and not juxtaposed DC-23B 315 A at 690 V AC-23A 400 A at 690 V AC-23B 500 A at 500 V AC-23A 500 A at 500 V AC-23B 630 A at 400 V AC-23A 630 A at 400 V AC-23B
Fuse type
BS
Fuse size
C1 C2
Network type
DC AC
Network frequency
50/60 Hz
Type of operating handle
External right side Direct frontal External frontal
mounting support
Plate
[Ui] rated insulation voltage
1000 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
12 kV
Rated operational power in W
295 kW at 690 V 355 kW at 400 V 355 kW at 500 V 400 kW at 690 V
Breaking capacity
5040 A at 400 V (AC-23B)
Making capacity
6300 A at 400 V AC-23B
Short-circuit withstand
70 kA
Mechanical durability
8000 cycles
Electrical durability
1000 cycles AC-23A 1000 cycles AC-23B 200 cycles DC-23A 200 cycles DC-23B
Connections - terminals
Power circuit: bars63 mm² Power circuit: lugs-ring terminals 2 cable(s) 150 mm² Power circuit: lugs-ring terminals 2 cable(s) 300 mm²
[Icm] rated short-circuit making capacity
80 kA at 400 V with protection by gG fuses
Tightening torque
Power circuit: 44 N.m
standards
IEC 60947-3
product certifications
CE
IP degree of protection
IP20 conforming to IEC 60529 (with terminal cover)
Ambient air temperature for operation
-20…70 °C
Ambient air temperature for storage
-40…80 °C
Fire resistance
850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1
height
300 mm
Width
364 mm
Depth
250 mm
Net weight
16 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
44.7 cm
Package 1 Width
41.7 cm
Package 1 Length
52.9 cm
Package 1 Weight
16.0 kg
Warranty
18 months