GS2GB4

FUSE DISCONNECT SW. 4X 63A A2-A3

Trade Price

£184.21

Per

1

Unit

EA

Pack Quantity

1

GS2GB4

Information

TeSys GS fuse switch-disconnector, 4 poles (4P), 63A/750V, to be used with type BS fuse links size A2-A3 up to 63A, for motor applications up to 30kW@400V AC-23. To be equipped with an external front side or right-hand side mounting operating handle GS2AH (several models available). It provides screw terminals with 4P terminal shrouds, high short circuit current rating 80kA@400V. Add-on auxiliary contact modules front mounting GS1AM (early-break and position signaling) can complete the assembly (to be ordered separately). Multi standards certified (IEC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Product name

TeSys GS

Device short name

GS2G

Product or component type

Switch-disconnector-fuse

Poles description

4P

Protected poles description

4t

Contacts type and composition

4 NO

[Ith] conventional free air thermal current

63 A (at 40 °C)

[Ie] rated operational current

40 A at 440 V 2 poles in series per phase DC-23A 40 A at 440 V 2 poles in series per phase DC-23B 63 A at 400 V AC-23A 63 A at 400 V AC-23B 63 A at 500 V AC-23A 63 A at 500 V AC-23B 63 A at 690 V AC-23A 63 A at 690 V AC-23B

Fuse type

BS

Fuse size

A3 A2

Network type

AC DC

Network frequency

50/60 Hz

Type of operating handle

External right side External frontal

mounting support

Plate

[Ui] rated insulation voltage

750 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

Rated operational power in W

30 kW at 400 V 40 kW at 500 V 55 kW at 690 V

Making capacity

630 A at 400 V AC-23B

Breaking capacity

500 A at 400 V (AC-23B)

Short-circuit withstand

10.6 kA

Mechanical durability

10000 cycles

Electrical durability

1500 cycles AC-23A 1500 cycles DC-23A 300 cycles AC-23B 300 cycles DC-23B

Connections - terminals

Power circuit: lugs-ring terminals10…25 mm²

[Icm] rated short-circuit making capacity

100 kA at 400 V with protection by gG fuses

Tightening torque

Power circuit: 3.2 N.m

standards

IEC 60947-3

product certifications

CE

IP degree of protection

IP20 conforming to IEC 60529 (with terminal cover)

Ambient air temperature for operation

-20…70 °C

Ambient air temperature for storage

-40…80 °C

Fire resistance

850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1

height

118 mm

Width

168 mm

Depth

116.5 mm

Net weight

1.3 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

12.5 cm

Package 1 Width

14.0 cm

Package 1 Length

19.5 cm

Package 1 Weight

1.488 kg

Unit Type of Package 2

S03

Number of Units in Package 2

6

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

9.429 kg

Warranty

18 months

Document Links

Datasheet