Trade Price
£634.55
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Product name
TeSys T
Device short name
LTMR
Product or component type
Motor controller
Device application
Equipment monitoring and control
Measurement current
5…100 A
[Us] rated supply voltage
100...240 V AC 50/60 Hz
Current consumption
8...62.8 mA
Supply voltage limits
93.5…264 V AC
Communication port protocol
Profibus DP
Bus type
Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, SUB-D 9 with 2 shielded twisted pairs, type A Profibus DP polarised 2-wire RS485 interface, addressing 1...125, transmission rate 9.6 kbit/s...12 Mbit/s, terminal block with 2 shielded twisted pairs, type A
[Ui] rated insulation voltage
690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508
[Uimp] rated impulse withstand voltage
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1
Short-circuit withstand
100 kA conforming to EN/IEC 60947-4-1
Associated fuse rating
4 A gG for output 0.5 A gG for control circuit
Protection type
Thermal overload protection Power factor variation Overload Locked rotor Thermal protection Reverse polarity protection Phase unbalance Earth-leakage protection Phase failure Load fluctuation Overload (long time)
Network and machine diagnosis type
Starting current and time Trip history information Running hours counter/operating time Phase fault and earth fault trip counters Trip context information Event recording Remaining operating time before overload tripping Motor control command recording Waiting time after overload tripping Fault recording
Logic input number
6
Input current
3.1 mA at 100 V 7.5 mA at 240 V
Current state 0 guaranteed
Logic input: 0...40 V and <= 15 mA for 25 ms
Current state 1 guaranteed
Logic input: 79...264 V and >= 2 mA for 25 ms
maximum output switching frequency
2 Hz
Load current
5 A at 250 V AC for logic output 5 A at 30 V DC for logic output
Permissible power
480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
Maximum operating rate
1800 cyc/h
Contacts type and composition
1 NO + 1 NC fault signal 3 NO
Metering type
Earth-fault current Phase current I1, I2, I3 RMS Temperature Imbalance current Average current Iavg
Measurement accuracy
5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 5 % active and reactive power 0,02 current
Overvoltage category
III
Connection pitch
5.08 mm
Connections - terminals
Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end
Tightening torque
Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm
Pollution degree
3
Electromagnetic compatibility
Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5
Width
91 mm
height
61 mm
Depth
122.5 mm
Net weight
0.53 kg
Web services
Web server
Compatibility code
LTMR
standards
EN 60947-4-1 IACS E10 CSA C22.2 No 14 UL 508 IEC 60947-4-1
product certifications
KERI RMRoS ABS UL ATEX NOM RINA BV CCC GL DNV CSA LROS (Lloyds register of shipping) EAC C-Tick
Protective treatment
12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068
Fire resistance
650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94
Ambient air temperature for operation
-20…60 °C
Ambient air temperature for storage
-40…80 °C
Operating altitude
<= 2000 m without derating
Mechanical robustness
Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
IP degree of protection
IP20
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
10 cm
Package 1 Width
7.2 cm
Package 1 Length
13.5 cm
Package 1 Weight
532 g
Unit Type of Package 2
S02
Number of Units in Package 2
10
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
5.649 kg
Warranty
18 months
Datasheet
Product Catalogue