LTMR08DBD

CONTROLLER DEVICENET 0.4 8A 24VDC

Trade Price

£669.41

Per

1

Unit

EA

Pack Quantity

1

LTMR08DBD

Information

TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. DeviceNet protocol is used by this controller. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 0.4 to 8 amperes. 24 VDC is used to power this controller. Controller is 2.40 inches tall, 3.58 inches wide and 4.82 inches deep. Controller weighs 1.17 lbs. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.

Technical Specifications

Range

TeSys

Product name

TeSys T

Device short name

LTMR

Product or component type

Motor controller

Device application

Equipment monitoring and control

Measurement current

0.4…8 A

[Us] rated supply voltage

24 V DC

Current consumption

56...127 mA

Supply voltage limits

20.4…26.24 V DC

Communication port protocol

DeviceNet

Bus type

DeviceNet ISO 1198 interface, addressing 1...64, transmission rate 125...500 kbit/s, terminal block with 4 twisted shielded pairs cable

[Ui] rated insulation voltage

690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508

[Uimp] rated impulse withstand voltage

6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1

Short-circuit withstand

100 kA conforming to EN/IEC 60947-4-1

Associated fuse rating

4 A gG for output 0.5 A gG for control circuit

Protection type

Thermal overload protection Overload Power factor variation Reverse polarity protection Earth-leakage protection Thermal protection Overload (long time) Phase failure Load fluctuation Phase unbalance Locked rotor

Network and machine diagnosis type

Fault recording Waiting time after overload tripping Remaining operating time before overload tripping Phase fault and earth fault trip counters Starting current and time Trip history information Trip context information Motor control command recording Running hours counter/operating time Event recording

Logic input number

6

Input current

7 mA

Current state 0 guaranteed

Logic input: < 5 V and <= 15 mA for 5 ms

Current state 1 guaranteed

Logic input: < 15 V and 2...15 mA for 15 ms

maximum output switching frequency

2 Hz

Load current

5 A at 250 V AC for logic output 5 A at 30 V DC for logic output

Permissible power

480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)

Maximum operating rate

1800 cyc/h

Contacts type and composition

1 NO + 1 NC fault signal 3 NO

Metering type

Phase current I1, I2, I3 RMS Temperature Earth-fault current Average current Iavg Imbalance current

Measurement accuracy

5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power

Overvoltage category

III

Connection pitch

5.08 mm

Connections - terminals

Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.25…2.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 1 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) solid without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) flexible with cable end Control circuit: connector 2 cable(s) 0.2…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.5…1.5 mm² (AWG 24...AWG 14) flexible without cable end Control circuit: connector 2 cable(s) 0.2…1 mm² (AWG 24...AWG 14) solid without cable end

Tightening torque

Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm

Pollution degree

3

Electromagnetic compatibility

Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 Voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 Temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 Temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 Control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 Relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5

Width

91 mm

height

61 mm

Depth

122.5 mm

Net weight

0.53 kg

Web services

Web server

Compatibility code

LTMR

standards

EN 60947-4-1 CSA C22.2 No 14 UL 508 IACS E10 IEC 60947-4-1

product certifications

LROS (Lloyds register of shipping) DNV GL UL C-Tick BV CSA ATEX RINA KERI CCC ABS EAC RMRoS NOM

Protective treatment

12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068

Fire resistance

650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94

Ambient air temperature for operation

-20…60 °C

Ambient air temperature for storage

-40…80 °C

Operating altitude

<= 2000 m without derating

Mechanical robustness

Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27

IP degree of protection

IP20

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

13.5 cm

Package 1 Width

7.0 cm

Package 1 Length

10.0 cm

Package 1 Weight

510.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

10

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

5.429 kg

Warranty

18 months

Document Links