Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Network rated voltage
400 V AC 50 Hz 415 V AC 50 Hz
Reactive power rating
75 kvar
Operating mode
Automatic
Range
PowerLogic
Device short name
automatic capacitor bank with detuned reactor
Product or component type
Capacitor bank
Network pollution level
Polluted
[Gh/Sn] harmonic pollution rate
25…50 %
[THDU] total harmonic distorsion of voltage
4…7 %
Tuning factor
3.8
Tuning frequency
190 Hz
Power per step
12.5 kvar
Step composition
2x12.5 + 2x25
Location of connection
Bottom
Controller type
PowerLogic PFC Controller VPL6
capacitor technology
PowerLogic PFC Capacitor + Detuned Reactor
Poles description
3P
capacitance tolerance
- 5 % to 10 %
[Ui] rated insulation voltage
690 V
[Uimp] rated impulse withstand voltage
8 kV
Maximum permissible voltage
1.1 x Un (8 hours over 24 hours) conforming to IEC 60831
[Imp] maximum permanent current
Capacitor: 1.8 x In at 480 V conforming to IEC 60831 Battery: 1.19 x In at 400 V conforming to IEC 61439-2 Battery: 1.19 x In at 415 V conforming to IEC 61439-2
main incomer protection
Without protection
[Icw] rated short-time withstand current
30 kA at 1 s (Icw)
Step protection type
Overload: step circuit breaker Short-circuit: step circuit breaker
accessibility for operation
Front
Colour
Grey (RAL 7035)
maximum weight
334 kg
height
1300 mm
Width
800 mm capacitor: 800 mm detuned reactor:
Depth
300 mm
provided equipment
Auxiliary transformer
Internal voltage transformer
400/230 V - 400 VA
Function available
Alarm contact GenSet shedding contact
Standards
IEC 61439-2 IEC 61439-1 IEC 61921
product certifications
EAC ASEFA CE
Mounting location
Indoor
IP degree of protection
Environment: IP31 Safety: IPxx B
IK degree of protection
IK10
Relative humidity
0…95 %
Operating altitude
<= 2000 m
ambient air temperature for operation
-5…45 °C
Average ambient air temperature for operation
35 °C (annual) 45 °C (over 24 hours)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Warranty
18 months
Datasheet