Trade Price
POA
Per
1
Unit
Pack Quantity
Range
TeSys
Product name
TeSys B
Product or component type
Contactor
Device short name
LC1BM
contactor application
Motor-heating-lighting
utilisation category
AC-3 AC-1
control circuit type
AC
Coil type
Standard
Poles description
3P
Pole contact composition
3 NO
[Ie] rated operational current
1250 A (at <40 °C) AC AC-1 for power circuit 1000 A (at <55 °C) AC AC-3 for power circuit
Motor power kW
530 kW at 1000 V AC 50/60 Hz (AC-3) 160 kW at 400 V AC 50/60 Hz (AC-4) 280 kW at 220...230 V AC 50/60 Hz (AC-3) 500 kW at 380...400 V AC 50/60 Hz (AC-3) 530 kW at 415 V AC 50/60 Hz (AC-3) 560 kW at 440 V AC 50/60 Hz (AC-3) 600 kW at 500 V AC 50/60 Hz (AC-3) 670 kW at 660...690 V AC 50/60 Hz (AC-3)
Auxiliary contact composition
2 NO + 2 NC
[Uc] control circuit voltage
220 V AC 50...400 Hz
Control circuit voltage limits
Drop-out: 0.3...0.5 Uc at 50...400 Hz Operational: 0.85...1.1 Uc at 50...400 Hz
[Ui] rated insulation voltage
1000 V - for power circuit conforming to IEC 60158-1 1000 V - for power circuit conforming to IEC 60947-4 1500 V - for power circuit conforming to VDE 0110 group C
Mounting mode
Fixed
mounting support
Notched mounting rails Bar support bracket
Tightening torque
Power circuit: 35 N.m - on bars
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 50/60 Hz
[Ith] conventional free air thermal current
1250 A (at 40 °C) for power circuit
Irms rated making capacity
10000 A at 1000 V AC for power circuit conforming to IEC 60158-1 10000 A at 1000 V AC for power circuit conforming to IEC 60947-4
Rated breaking capacity
10000 A at 440 V for power circuit conforming to IEC 60158-1 10000 A at 440 V for power circuit conforming to IEC 60947-4 4000 A at 1000 V for power circuit conforming to IEC 60158-1 4000 A at 1000 V for power circuit conforming to IEC 60947-4 8000 A at 660...690 V for power circuit conforming to IEC 60158-1 8000 A at 660...690 V for power circuit conforming to IEC 60947-4 9000 A at 500 V for power circuit conforming to IEC 60158-1 9000 A at 500 V for power circuit conforming to IEC 60947-4
Associated fuse rating
1200 A aM at <= 440 V for power circuit 1200 A gI at <= 440 V for power circuit 1500 A gI at <= 440 V for power circuit
Average impedance
0.18 mOhm - Ith 1250 A 50 Hz for power circuit
Power dissipation per pole
180 W AC-3 - Ith 1250 A 280 W AC-1 - Ith 1250 A
Inrush power in VA
1300 VA
Hold-in power consumption in VA
31 VA 50/60 Hz
Operating time
100...150 ms closing 50...100 ms opening
Mechanical durability
1200000 cycles
Maximum operating rate
120 cyc/h 55 °C
height
490 mm
Width
570 mm
Depth
475 mm
Net weight
57 kg
Standards
VDE 0660 BS 5424 IEC 60947-4 IEC 60158-1 NF C 63-110
product certifications
RINA CSA BV
Protective treatment
TC TH
ambient air temperature for operation
-5…55 °C
Ambient air temperature for storage
-60…80 °C
Operating altitude
3000 m without derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
60 cm
Package 1 Width
68 cm
Package 1 Length
54 cm
Package 1 Weight
54 kg
Warranty
18 months
Datasheet