Trade Price
POA
Per
1
Unit
Pack Quantity
Product or component type
Passive filter
Product specific application
Reduction of current harmonics
range compatibility
Altivar 71 Altivar Process ATV900 Altivar 61 Altivar Process ATV600
[Us] rated supply voltage
400 V +/- 10 %
power supply frequency
50 Hz +/- 2 %
Quantity per drive
1 filter per drive for variable speed drive ATV61W motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV61H motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV71H motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV71W motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV650 wall mount, motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV630 wall mount, motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV950 wall mount, motor: 15 kW/20 hp 1 filter per drive for variable speed drive ATV930 wall mount, motor: 15 kW/20 hp
[In] rated current
29 A for input 30 A for output
Network number of phases
3 phases
THDI
10 % for variable speed drive ATV61W motor: 15 kW/20 hp 16 % for variable speed drive ATV61H motor: 15 kW/20 hp 16 % for variable speed drive ATV71H motor: 15 kW/20 hp 16 % for variable speed drive ATV71W motor: 15 kW/20 hp 10 % for variable speed drive ATV650 motor: 15 kW/20 hp 10 % for variable speed drive ATV630 motor: 15 kW/20 hp 10 % for variable speed drive ATV950 motor: 15 kW/20 hp 10 % for variable speed drive ATV930 motor: 15 kW/20 hp
Max current
1.5 x nominal current (duration = 60 s)
Efficiency
98 %
Thermal losses
224 W
Cos phi
1 (150 % of line current) 0.85 (75 % of line current) 0.99 (100 % of line current)
Electrical connection
X1-1...X2-3 terminal, connection capacity: 0.5...10 mm² A, B terminal, connection capacity: 2.5 mm²
Electrical insulation class
Class F
Net weight
25 kg
IP degree of protection
IP20 IP55 (enclosure mounting)
Vibration resistance
2 mm peak to peak (f= 5…13.2 Hz) conforming to EN 60068-2-6 0.7 gn (f= 13.2…150 Hz) conforming to EN 60068-2-6
Relative humidity
5…85 % without condensation
Ambient air temperature for operation
45…60 °C (with current derating 3 % per °C) 5…45 °C (without current derating)
Ambient air temperature for storage
-25…55 °C storage in original packaging -25…65 °C during transport
Operating altitude
<= 1000 m without current derating > 1000...4000 m with current derating 5 % per 1000 m
standards
EN/IEC 61000-3-4 G5/4 engineering recommendation EN/IEC 61000-3-12 EN/IEC 61000-3-2 EN/IEC 61000-2-4 EN/IEC 61000-2-2
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
56.000 cm
Package 1 Width
40.000 cm
Package 1 Length
59.000 cm
Package 1 Weight
32.200 kg
Unit Type of Package 2
P06
Number of Units in Package 2
2
Package 2 Height
75.000 cm
Package 2 Width
60.000 cm
Package 2 Length
80.000 cm
Package 2 Weight
72.900 kg
Warranty
18 months