IMDIFL12C

VIGILOHM 12CH. LOC. MODB. 110-440

Trade Price

£1,027.03

Per

1

Unit

EA

Pack Quantity

1

IMDIFL12C

Information

This device belongs to the Vigilohm range designed to monitor ungrounded/IT electrical networks at feeder level, in accordance to installation and products standards This insulation fault location is only possible when it is associated to IM400 series, XM300 or XM200. This device is dedicated to monitoring 12 feeders, AC, DC and ACDC, up to the toroid limit, 1000V. Configuration is set from the front of the device, through the HMI screen, or from the communication port. Settings are related to alarm thresholds. It displays which feeder has an insulation fault. Auto-test starts automatically every 5 hours, and on demand. In case the insulation resistance drops below the set threshold, an alarm is triggered thru the IFL output relay and HMI. Once no fault is monitored, the alarm is cleared, the alarm relay is back to normal. The device can be supplied by a 110VAC to 440VAC source or a 110VDC to 440VDC, all with a tolérence of plus or minus 15%.

Technical Specifications

Range

Vigilohm

Device short name

IFL12C

Product or component type

Insulation fault locator

Device application

Standard environment application Marine application

electrical circuit type

Medium or low disturbed network

Electrical circuit type

Power circuit

Earthing system

IT

User language

Portuguese Russian Chinese French Spanish Italian German English

Network rated voltage

0…1000 V - AC at 45...65 Hz 0…1000 V - DC

Number of channels

12

Local signalling

Yellow indicator light: insulation fault Yellow flashing indicator light: communication Green/red indicator light: product status Green indicator light: satisfactory insulation Yellow flashing indicator light: transient fault

Threshold setting

Alarm: high, medium, low

alarm per channel

Alarm threshold: common to all feeders

Response time

<= 5 s

auxiliary supply voltage

100...440 V DC +/- 15 % 100...440 V AC 45...65 Hz +/- 15 %

Power consumption in VA

26 VA

Power consumption in W

10 W

Test function

Auto test at start and every 5h Remote test Manual

output contact

1 C/O standard or fail-safe

breaking capacity

250 V - AC at 6 A 48 V - DC at 1 A

Communication port protocol

Modbus

Communication port support

RS485

Display type

Digital display

Mounting mode

Flush-mounted Clip-on

mounting support

DIN rail Panel

Mounting position

Horizontal Vertical

Connections - terminals

Power supply: removable screw terminal block0.2…2.5 mm² Output relay: removable screw terminal block0.2…2.5 mm² Toroids inputs: removable screw terminal block0.2…1.5 mm² Communication: removable screw terminal block0.2…2.5 mm²

Material

Thermoplastic

Overvoltage category

III

Net weight

0.5 kg

Cut-out dimensions

92 x 104 mm

height

110 mm

Width

108 mm

Depth

59 mm

IP degree of protection

Case: IP20 Front face: IP54

Environmental characteristic

Exposure to damp heat not in service conforming to IEC 60068-2-30 Exposure to damp heat in service conforming to IEC 60068-2-56 Salt mist conforming to IEC 60068-2-52

Operating altitude

<= 3000 m

Pollution degree

2

Relative humidity

5…92 %

Type of installation

Indoor

Standards

IEC 60364-4-41 IEC 61010-1 IEC 60364-5-51 IEC 61557-9

product certifications

EAC CE DNV-GL UL cULus

Ambient air temperature for operation

-25…55 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

9.7 cm

Package 1 Width

18.2 cm

Package 1 Length

13.5 cm

Package 1 Weight

550.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

8

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

5.2 kg

Warranty

18 months

Document Links

Datasheet