TM3TI4G

MODULE TM3-4 INPUTS TEMP SPRING

Trade Price

£248.44

Per

1

Unit

EA

Pack Quantity

1

TM3TI4G

Information

This product is part of the Modicon TM3 range, an offer of expansion I/O modules for Modicon M221, M241, M251 and M262. The analogue input module provides 4 inputs with 16bit and 15bit + sign resolution. It is an input module with a rated supply voltage of 24V DC and a current consumption of 45mA/50mA at 5V DC via bus connector, 35mA/40mA at 24V DC via external supply. This product is capable of controlling variable speed drives or any device equipped with a current or voltage input. There is an insulation between input and supply at 1500V AC, input and internal logic at 500V AC. It is furnished with removable spring terminal for electrical connection with pitch 3.81mm adjustment for inputs and supply. It is an IP20 rated product. Its dimensions are 23.6mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.1kg. This product is certified by CE. It meets EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. This module is compatible with Modicon M262, Modicon M241, Modicon M251 and Modicon M221 logic controller. It supports top hat type TH35-15, top hat type TH35-7.5 rail conforming to IEC 60715 and plate or panel with fixing kit mount. Modicon TM3 expansion modules have been designed with a simple interlocking assembly mechanism. A bus expansion connector is used to distribute data and the power supply when assembling the Modicon TM3 modules with logic controllers. Boost the performance of your controller with the Modicon TM3 I/O system specially designed for the Modicon M221, M241 and M251 logic controllers.

Technical Specifications

Range of product

Modicon TM3

Product or component type

Analog input module

range compatibility

Modicon M221 Modicon M241 Modicon M251 Modicon M262

analogue input number

4

Analogue input type

current 4...20 mA current 0...20 mA voltage 0...10 V voltage - 10...10 V thermocouple - 200...1000 °C with thermocouple J thermocouple - 200...1300 °C with thermocouple K thermocouple 0...1760 °C with thermocouple R thermocouple 0...1760 °C with thermocouple S thermocouple 0...1820 °C with thermocouple B thermocouple - 200...400 °C with thermocouple T thermocouple - 200...1300 °C with thermocouple N thermocouple - 200...800 °C with thermocouple E thermocouple 0...2315 °C with thermocouple C Pt 100 temperature probe - 200...850 °C Pt 1000 temperature probe - 200...600 °C

Analogue input resolution

16 bits 15 bits + sign

Permissible continuous overload

13 V, analogue input type: voltage 40 mA, analogue input type: current

Input impedance

<= 50 Ohm current >= 1 MOhm voltage >= 1 MOhm thermocouple >= 1 MOhm temperature probe

LSB value

2.44 mV 0...10 Vvoltage 4.88 mV - 10...10 Vvoltage 4.88 µA 0...20 mAcurrent 3.91 µA 4...20 mAcurrent 0.1 °Ctemperature probe 0.1 °Cthermocouple

Conversion time

100 ms + 100 ms per channel + 1 controller cycle time for analogue input thermocouple 100 ms + 100 ms per channel + 1 controller cycle time for analogue input temperature probe 10 ms + 10 ms per channel + 1 controller cycle time for analogue input voltage/current

Sampling duration

10 ms, analogue input type: voltage/current 100 ms, analogue input type: voltage/current 100 ms, analogue input type: thermocouple 100 ms, analogue input type: temperature probe

Absolute accuracy error

+/- 0.2 % of full scale at 25 °C for analogue input voltage/current +/- 0.2 % of full scale at 25 °C for Pt 100/Pt 1000, Ni 100/ Ni 1000 temperature probe +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C +/- 6 °C at 25 °C for thermocouple R, S 0...200 °C +/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C +/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C +/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C +/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C +/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C +/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C +/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C +/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C

Temperature drift

+/- 0.01 %FS/°C

Repeat accuracy

+/-0.5 %FS

Non-linearity

+/- 0.2 %FS

Cross talk

<= 1 LSB

[Us] rated supply voltage

24 V DC

Supply voltage limits

20.4…28.8 V

Type of cable

Twisted shielded pairs cable <30 m for input circuit

Current consumption

45 mA at 5 V DC via bus connector 50 mA at 5 V DC via bus connector 35 mA at 24 V DC via external supply 40 mA at 24 V DC via external supply

Local signalling

1 LED (green) for PWR

Electrical connection

10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs and supply 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for inputs

Insulation

Between input and supply at 1500 V AC Between input and internal logic at 500 V AC

Marking

CE

Surge withstand

1 kV power supply common mode conforming to EN/IEC 61000-4-5 0.5 kV power supply differential mode conforming to EN/IEC 61000-4-5 1 kV input common mode conforming to EN/IEC 61000-4-5

Mounting support

Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit

height

90 mm

Depth

70 mm

Width

23.6 mm

Net weight

0.1 kg

standards

EN/IEC 61131-2

product certifications

CE UKCA RCM EAC cULus cULus HazLoc

Resistance to electrostatic discharge

8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2

Resistance to electromagnetic fields

10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3

Resistance to magnetic fields

30 A/m conforming to EN/IEC 61000-4-8

Resistance to fast transients

1 kV (I/O) conforming to EN/IEC 61000-4-4

Resistance to conducted disturbances

10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)

Electromagnetic emission

Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011

Immunity to microbreaks

10 ms

Ambient air temperature for operation

-10…55 °C horizontal installation -10…35 °C vertical installation

Ambient air temperature for storage

-25…70 °C

Relative humidity

10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)

IP degree of protection

IP20

Pollution degree

2

Operating altitude

0...2000 m

Storage altitude

0…3000 m

Vibration resistance

3.5 mm at 5…8.4 Hz on DIN rail 3 gn at 8.4…150 Hz on DIN rail

Shock resistance

15 gn for 11 ms

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

7.5 cm

Package 1 Width

12.5 cm

Package 1 Length

10.5 cm

Package 1 Weight

201.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

9

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

2.273 kg

Unit Type of Package 3

P12

Number of Units in Package 3

432

Package 3 Height

80 cm

Package 3 Width

105 cm

Package 3 Length

125 cm

Package 3 Weight

111.832 kg

Warranty

18 months

Document Links

Datasheet