This product is part of the Modicon M221 range, an offer of programmable logic controllers for hardwired architectures. This logic controller provides 24 discrete inputs and 16 relay ethernet outputs with 10bit input resolution, normally opened relay output. It is a Modicon logic controller with a rated supply voltage of 100V to 240V AC, an output voltage of 5V to 125V DC, 5V to 250V AC and an output current of 2A with sink or source input logic. This product requires minimal installation and offers tremendous versatility. Integrated connections are USB port with mini B USB 2.0 connector, non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface and ethernet with RJ45 connector. It is a Modicon M221 controller with a network frequency of 50/60Hz, 256KB for internal variables RAM, user application and data RAM, a built-in flash memory of 256KB and a SD card memory capacity of 2GB. It is an IP20 rated product. Its dimensions are 160mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.456kg. This product is certified by CE, IACS E10, RCM, ABS, LR, DNV-GL, CSA, EAC and CULus. It meets EN/IEC 60664-1, EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. It supports DIN rail mount. Achieve benchmark performance while increasing profitability with the Modicon M221 through intuitive machine programming with SoMachine Basic, ready-to-use applications and function blocks
Range of product
Modicon M221
Product or component type
Logic controller
[Us] rated supply voltage
100...240 V AC
Discrete input number
24, discrete input conforming to IEC 61131-2 Type 1
Analogue input number
2 at 0...10 V
Discrete output type
Relay normally open
Discrete output number
16 relay
Discrete output voltage
5...125 V DC 5...250 V AC
Discrete output current
2 A
Discrete I/O number
40
Maximum number of I/O expansion module
7 (local I/O-Architecture) 14 (remote I/O-Architecture)
Supply voltage limits
85…264 V
Network frequency
50/60 Hz
Inrush current
40 A
Maximum power consumption in VA
70 VA at 100...240 V with max number of I/O expansion module 41 VA at 100...240 V without I/O expansion module
Power supply output current
0.52 A 5 V for expansion bus 0.24 A 24 V for expansion bus
Discrete input logic
Sink or source (positive/negative)
Discrete input voltage
24 V
discrete input voltage type
DC
analogue input resolution
10 bits
LSB value
10 mV
Conversion time
1 ms per channel + 1 controller cycle time for analogue input analog input
Permitted overload on inputs
+/- 30 V DC for 5 min (maximum) for analog input +/- 13 V DC (permanent) for analog input
Voltage state 1 guaranteed
>= 15 V for input
Voltage state 0 guaranteed
<= 5 V for input
Discrete input current
7 mA for discrete input 5 mA for fast input
Input impedance
3.4 kOhm for discrete input 100 kOhm for analog input 4.9 kOhm for fast input
Response time
35 µs turn-off, I2...I5 terminal(s) for input 10 ms turn-on for output 10 ms turn-off for output 5 µs turn-on, I0, I1, I6, I7 terminal(s) for fast input 35 µs turn-on, other terminals terminal(s) for input 5 µs turn-off, I0, I1, I6, I7 terminal(s) for fast input 100 µs turn-off, other terminals terminal(s) for input
Configurable filtering time
0 ms for input 3 ms for input 12 ms for input
Output voltage limits
125 V DC 277 V AC
Maximum current per output common
7 A
Absolute accuracy error
+/- 1 % of full scale for analog input
Electrical durability
100000 cycles AC-12, 120 V, 240 VA, resistive 100000 cycles AC-12, 240 V, 480 VA, resistive 300000 cycles AC-12, 120 V, 80 VA, resistive 300000 cycles AC-12, 240 V, 160 VA, resistive 100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive 100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive 300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive 100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive 300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive 100000 cycles DC-12, 24 V, 48 W, resistive 300000 cycles DC-12, 24 V, 16 W, resistive 100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms) 300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
Switching frequency
20 switching operations/minute with maximum load
Mechanical durability
20000000 cycles for relay output
Minimum load
1 mA at 5 V DC for relay output
Protection type
Without protection at 5 A
Reset time
1 s
Memory capacity
256 kB for user application and data RAM with 10000 instructions 256 kB for internal variables RAM
Data backed up
256 kB built-in flash memory for backup of application and data
Data storage equipment
2 GB SD card (optional)
Battery type
BR2032 or CR2032X lithium non-rechargeable
Backup time
1 year at 25 °C (by interruption of power supply)
Execution time for 1 KInstruction
0.3 ms for event and periodic task
Execution time per instruction
0.2 µs Boolean
Exct time for event task
60 µs response time
Maximum size of object areas
8000 %MW memory words 255 %TM timers 512 %KW constant words 255 %C counters 512 %M memory bits
Realtime clock
With
Clock drift
<= 30 s/month at 25 °C
Regulation loop
Adjustable PID regulator up to 14 simultaneous loops
Counting input number
4 fast input (HSC mode) at 100 kHz 32 bits
counter function
Single phase A/B Pulse/direction
Integrated connection type
USB port with mini B USB 2.0 connector Non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface Ethernet with RJ45 connector
Supply
(serial)serial link supply: 5 V, <200 mA
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for USB
Communication port protocol
USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network Ethernet
Port Ethernet
10BASE-T/100BASE-TX 1 port with 100 m copper cable
Communication service
DHCP client Modbus TCP client Ethernet/IP adapter Modbus TCP server Modbus TCP slave device
Local signalling
1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED per channel (green) for I/O state 1 LED (green) for SL Ethernet network activity (green) for ACT Ethernet network link (yellow) for Link (Link Status)
Electrical connection
removable screw terminal block for inputs removable screw terminal block for outputs terminal block, 3 terminal(s) for connecting the 24 V DC power supply connector, 4 terminal(s) for analogue inputs Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devices
Shielded cable: <10 m for fast input Unshielded cable: <30 m for output Unshielded cable: <30 m for digital input Unshielded cable: <1 m for analog input
Insulation
Between input and internal logic at 500 V AC Non-insulated between analogue input and internal logic Non-insulated between analogue inputs Between supply and ground at 1500 V AC Between sensor power supply and ground at 500 V AC Between input and ground at 500 V AC Between output and ground at 1500 V AC Between supply and internal logic at 2300 V AC Between sensor power supply and internal logic at 500 V AC Between output and internal logic at 2300 V AC Between Ethernet terminal and internal logic at 500 V AC Between supply and sensor power supply at 2300 V AC
Marking
CE
Sensor power supply
24 V DC at 250 mA supplied by the controller
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
height
90 mm
Depth
70 mm
Width
160 mm
Net weight
0.456 kg
standards
EN/IEC 61131-2 UL 508 CAN/CSA C22.2 No. 213 IACS E10 ANSI/ISA 12-12-01
product certifications
DNV-GL EAC ABS cULus LR RCM CE UKCA cULus HazLoc
Environmental characteristic
Ordinary and hazardous location
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields
30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4
Surge withstand
2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 200…1000 MHz conforming to EN/IEC 55011
Immunity to microbreaks
10 ms
Ambient air temperature for operation
-10…55 °C (horizontal installation) -10…35 °C (vertical installation)
Ambient air temperature for storage
-25…70 °C
Relative humidity
10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
IP degree of protection
IP20 with protective cover in place
Pollution degree
<= 2
Operating altitude
0...2000 m
Storage altitude
0…3000 m
Vibration resistance
3.5 mm at 5…8.4 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 1 gn at 8.4…150 Hz on symmetrical rail 1 gn at 8.4…150 Hz on panel mounting
Shock resistance
98 m/s² for 11 ms
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
11.09 cm
Package 1 Width
14.183 cm
Package 1 Length
21.085 cm
Package 1 Weight
830.0 g
Unit Type of Package 2
CAR
Number of Units in Package 2
12
Package 2 Height
29.2 cm
Package 2 Width
39.8 cm
Package 2 Length
57.9 cm
Package 2 Weight
11.04 kg
Unit Type of Package 3
P12
Number of Units in Package 3
144
Package 3 Height
105.0 cm
Package 3 Width
120.0 cm
Package 3 Length
80.0 cm
Package 3 Weight
145 kg
Warranty
18 months
Datasheet