This communication module is proposed as an option Modicon M241/251 controllers. This module provides slave Profibus DP. It is equipped with a 9-way SUB-D connector.
Product or component type
Profibus DP communication module
range compatibility
Modicon M251 Modicon M241
Product compatibility
Modicon M241 logic controller Modicon M251 logic controller
Current consumption
290 mA at 5 V DC for communication bus
Power dissipation in W
1.5 W
Integrated connection type
Profibus DP: female SUB-D 9 connector
Transmission rate
1.5 Mbit/s for bus length of 200 m 500 kbit/s for bus length of 400 m 187.5 kbit/s for bus length of 1000 m 9.6...93.75 kbit/s for bus length of 1200 m 3...12 Mbit/s for bus length of 100 m
Communication port protocol
Profibus DP V0 Profibus DP V1
Insulation
Between bus and internal logic at 1000 V DC
Local signalling
1 LED (green/yellow) for power supply 1 LED (green/red) for communication
Electrical connection
Screw connector terminal for connecting the functional ground SUB-D 9 1 female connector for connecting Profibus
Marking
CE
Surge withstand
1 kV power lines (DC) common mode conforming to EN/IEC 61000-4-5 2 kV power lines (AC) common mode conforming to EN/IEC 61000-4-5 2 kV relay output common mode conforming to EN/IEC 61000-4-5 1 kV I/O common mode conforming to EN/IEC 61000-4-5 1 kV shielded cable common mode conforming to EN/IEC 61000-4-5 0.5 kV power lines (DC) differential mode conforming to EN/IEC 61000-4-5 1 kV power lines (AC) differential mode conforming to EN/IEC 61000-4-5 1 kV relay output differential mode conforming to EN/IEC 61000-4-5 0.5 kV I/O differential mode conforming to EN/IEC 61000-4-5
Mounting support
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
Width
25 mm
height
90 mm
Depth
90 mm
Net weight
0.1 kg
standards
EN/IEC 61131-2 UL 508 EIA-485
product certifications
C-Tick cULus
Resistance to electrostatic discharge
8 kV in air conforming to EN/IEC 61000-4-2 4 kV on contact conforming to EN/IEC 61000-4-2 8 kV in air conforming to Marine specification (LR, ABS, DNV, GL) 6 kV on contact conforming to Marine specification (LR, ABS, DNV, GL)
Resistance to electromagnetic fields
10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3 1 V/m 2...2.7 GHz conforming to EN/IEC 61000-4-3
Resistance to fast transients
2 kV (power lines) conforming to EN/IEC 61000-4-4 2 kV (relay output) conforming to EN/IEC 61000-4-4 1.5 kV (I/O) conforming to EN/IEC 61000-4-4 1 kV (Ethernet line) conforming to EN/IEC 61000-4-4 1 kV (serial link) conforming to EN/IEC 61000-4-4
Resistance to conducted disturbances
10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Conducted emissions - test level: 79 dBμV/m QP/66 dBμV/m AV ( power lines (AC)) at 0.15…0.5 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 73 dBμV/m QP/60 dBμV/m AV ( power lines (AC)) at 0.5…300 MHz conforming to EN/IEC 55011 Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to EN/IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A at 30…230 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 60...54 dBμV/m QP at 30…100 MHz conforming to Marine specification (LR, ABS, DNV, GL) Radiated emissions - test level: 24 dBμV/m QP at 156…165 MHz conforming to Marine specification (LR, ABS, DNV, GL) Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to EN/IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A at 230…1000 MHz conforming to EN/IEC 55011 Radiated emissions - test level: 80...50 dμV/m QP at 150…30000 kHz conforming to Marine specification (LR, ABS, DNV, GL) Radiated emissions - test level: 54 dBμV/m QP at 100…2000 MHz conforming to Marine specification (LR, ABS, DNV, GL)
Ambient air temperature for operation
-10…55 °C horizontal installation -10…50 °C vertical installation
Ambient air temperature for storage
-25…70 °C
Relative humidity
10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
IP degree of protection
IP20 with protective cover in place
Pollution degree
2
Operating altitude
0...2000 m
Storage altitude
0…3000 m
Vibration resistance
1 mm at 5…13.2 Hz on symmetrical rail 3 gn at 8.7…150 Hz on symmetrical rail 1 mm at 5…13.2 Hz on panel mounting 0.7 gn at 13.2…100 Hz on panel mounting
Shock resistance
15 gn for 11 ms
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
17.0 cm
Package 1 Width
11.0 cm
Package 1 Length
5.4 cm
Package 1 Weight
210.0 g
Unit Type of Package 2
S03
Number of Units in Package 2
34
Package 2 Height
30 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
7.15 kg