Trade Price
POA
Per
1
Unit
Pack Quantity
This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.
Range of produc
Harmony Control Relays
Relay type
Current control relay
Product or component type
Current control relay
Relay name
RM35JA
Relay monitored parameters
Overcurrent or undercurrent in window mode Overcurrent or undercurrent detection
time delay
Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Switching capacity in VA
2000 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
8 A AC
Maximum power consumption in VA
3.5 VA
Measurement range
0.15...1.5 A E1-M terminals 0.5...5 A E2-M terminals 1.5...15 A E3-M terminals 150 mA...15 A current AC/DC 50/60 Hz
Utilisation category
AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1
Contacts type and composition
2 C/O
Reset time
1500 ms at maximum voltage
Maximum switching voltage
250 V AC
Supply voltage limits
20.4…264 V AC/DC
operating voltage tolerance
- 15 % + 10 % Un
Maximum power consumption in W
1.5 W DC
Resistance across terminals
0.005 Ohm at E3-M terminals 0.015 Ohm at E2-M terminals 0.05 Ohm at E1-M terminals
Output contacts
2 C/O
Nominal output current
8 A
Maximum measuring cycle
100 ms measurement cycle as true rms value
Internal input resistance
0.015 Ohm 0.005 Ohm 0.05 Ohm
Setting accuracy of the switching threshold
+/- 10 % of the full scale
Switching threshold drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
Setting accuracy of time delay
10 P
Time delay drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
Hysteresis
5…50 % adjustable of threshold setting 3 % fixed of full scale for window mode
delay at power up
0.3 s
Repeat accuracy
+/- 0.5 % for input and measurement circuit +/- 2 % for time delay
Measurement error
< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
Response time
<= 500 ms (on crossing the threshold)
Threshold setting
10...100 %
Overvoltage category
III conforming to IEC 60664-1 III conforming to UL 508
Insulation resistance
> 100 MOhm at 500 V DC conforming to IEC 60255-27
insulation
Between supply and measurement
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Tightening torque
0.6…1 N.m conforming to IEC 60947-1
Housing material
Self-extinguishing plastic
Local signalling
LED (yellow) for relay ON LED (green) for power ON
Mounting support
35 mm DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
10000000 cycles
Safety reliability data
MTTFd = 296.8 years B10d = 270000
Contacts material
Cadmium free
Width
35 mm
Net weight
0.12 kg
Immunity to microbreaks
50 ms
Electromagnetic compatibility
Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for industrial environments conforming to IEC 61000-6-4 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22 Emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3
Standards
IEC 60255-1
product certifications
CE GL CCC EAC RCM UL CSA
Ambient air temperature for storage
-40…70 °C
Ambient air temperature for operation
-20…50 °C at 60 Hz -20…60 °C at 50 Hz
Environmental characteristic
3K3 C
Relative humidity
93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance
0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance
15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protection
IP20 (terminals) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529 IP30 (housing) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1 3 conforming to UL 508
Dielectric test voltage
2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.8 cm
Package 1 Width
4.5 cm
Package 1 Length
9.5 cm
Package 1 Weight
131 g
Unit Type of Package 2
S02
Number of Units in Package 2
32
Package 2 Height
15 cm
Package 2 Width
30 cm
Package 2 Length
40 cm
Package 2 Weight
4.647 kg
Warranty
18 months
Datasheet