RM22UB34

VOLTAGE CONTROL RELAY

Trade Price

POA

Per

1

Unit

Pack Quantity

RM22UB34
RM22UB34
RM22UB34
RM22UB34

Information

This Harmony RM22-UB relay allows monitoring of voltage control in single phase networks. This modular multi function single phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slim form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.

Technical Specifications

Range of produc

Harmony Control Relays

Relay type

Voltage control relay

Product or component type

Voltage control relay

Network number of phases

1 phase

Supply circuit type

AC/DC

Relay name

RM22UA

Relay monitored parameters

Overvoltage and undervoltage detection

time delay

Adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt

Switching capacity in VA

2000 VA

Minimum switching current

10 mA at 5 V DC

Maximum switching current

8 A AC

Power consumption in VA

5 VA AC

Measurement range

80...300 V voltage AC/DC 50/60 Hz

Utilisation category

AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1

Contacts type and composition

2 C/O

Reset time

1500 ms at maximum voltage

Maximum switching voltage

250 V AC

Supply voltage limits

60…280 V AC

Maximum power consumption in W

2 W DC

Immunity to microbreaks

20 ms

Output contacts

2 C/O

Nominal output current

8 A

Maximum measuring cycle

250 ms measurement cycle as true rms value

Hysteresis

5…50 % adjustable of threshold setting

delay at power up

600 ms

Repeat accuracy

+/- 0.5 % for input and measurement circuit +/- 2 % for time delay

Measurement error

< 1 % over the whole range with voltage variation 0.2 %/°C with temperature variation

Response time

<= 500 ms

Overvoltage category

III conforming to IEC 60664-1

Insulation resistance

> 100 MOhm at 500 V DC

Connections - terminals

Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end

Tightening torque

0.6…1 N.m conforming to IEC 60947-1

Housing material

Self-extinguishing plastic

Mounting support

35 mm DIN rail conforming to IEC 60715

Electrical durability

100000 cycles

Mechanical durability

10000000 cycles

Contacts material

Cadmium free

Safety reliability data

MTTFd = 433.7 years B10d = 400000

Width

22.5 mm

Net weight

0.09 kg

Functionality

Overvoltage and undervoltage detection

Compatibility code

RM22

Electromagnetic compatibility

Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Emission standard for industrial environments conforming to IEC 61000-6-4 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22

Standards

IEC 60255-1

product certifications

CCC CE CSA EAC UL GL RCM

Ambient air temperature for storage

-40…70 °C

Ambient air temperature for operation

-20…50 °C at 60 Hz -20…60 °C at 50 Hz

Relative humidity

93…97 % at 25…55 °C conforming to IEC 60068-2-30

Vibration resistance

0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6

Shock resistance

15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27

IP degree of protection

IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529

Pollution degree

3 conforming to IEC 60664-1

Dielectric test voltage

2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

2.6 cm

Package 1 Width

8.2 cm

Package 1 Length

9.5 cm

Package 1 Weight

104.0 g

Unit Type of Package 2

S02

Number of Units in Package 2

40

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

4.58 kg

Unit Type of Package 3

P06

Number of Units in Package 3

640

Package 3 Height

80.0 cm

Package 3 Width

80.0 cm

Package 3 Length

60.0 cm

Package 3 Weight

86.18 kg

Warranty

18 months

Document Links

Datasheet