Pack Quantity
This Harmony RE22 timing relay can be set between 0.05 seconds and 300 hours, has an output rating of 8A, is 22.5mm wide and can be supplied with 24V to 240V AC. It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail. It also offers a sealable cover, simple and precise settings with rotary trimmers. multi function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. Status display with 2 LEDs, visually inspect the status of you system without specialized tools. Diagnostic button allows simple setup and trouble shooting by non-specialists. 0 0 0 0 0 0 0 0 0 0 0 0 0
Range of product
Harmony Timer Relays
Product or component type
Multifunction relay
Discrete output type
Relay
Device short name
RE22
Nominal output current
8 A
Contacts type and composition
1 C/O timed or instantaneous contact, cadmium free 2 C/O timed contact, cadmium free
Time delay type
Power on-delay Off-delay Symmetrical flashing Interval Star-delta
Time delay range
3...30 min 30...300 min 0.3...3 s 3...30 h 10...100 s 1...10 s 0.05...1 s 30...300 s 30...300 h 3...30 s
Control type
Rotary knob Diagnostic button Potentiometer external
[Us] rated supply voltage
24...240 V AC/DC 50/60 Hz
Release input voltage
<= 2.4 V
Voltage range
0.85...1.1 Us
Supply frequency
50...60 Hz +/- 5 %
Connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque
0.6…1 N.m conforming to IEC 60947-1
Housing material
Self-extinguishing
Repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
Temperature drift
+/- 0.05 %/°C
Voltage drift
+/- 0.2 %/V
Setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width
100 ms with load in parallel 30 ms
Insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1
Recovery time
120 ms on de-energisation
Immunity to microbreaks
10 ms
Power consumption in VA
3 VA at 240 V AC
Power consumption in W
1.5 W at 240 V DC
Switching capacity in VA
2000 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
8 A
Maximum switching voltage
250 V AC
Electrical durability
100000 cycles, 8 A at 250 V, AC-1 100000 cycles, 2 A at 24 V, DC-1
Mechanical durability
10000000 cycles
Rated impulse withstand voltage
5 kV for 1.2…50 µs conforming to IEC 60664-1
Power on delay
100 ms
Creepage distance
4 kV/3 conforming to IEC 60664-1
Overvoltage category
III conforming to IEC 60664-1
Safety reliability data
B10d = 160000 MTTFd = 171.2 years
Mounting position
Any position
Mounting support
35 mm DIN rail conforming to IEC 60715
Status LED
LED backlight green (steady) for dial pointer indication LED yellow (steady) for output relay energised LED yellow (fast flashing) for timing in progress and output relay de-energised LED yellow (slow flashing) for timing in progress and output relay energised
Function available
A- Power on-delay relay-2 C/O At- Power on-delay relay w/ pause/summation (X1)-2 C/O Aw- Power on-delay relay w/ retrigger/restart-2 C/O C- Off-delay relay w/ control signal-2 C/O Ct- Off-delay relay w/ control signal and pause/summation-2 C/O D- Symmetrical flashing relay (starting pulse-off)-2 C/O Dt- Symmetrical flashing relay (starting pulse-off) w/ pause/summation (X1)-2 C/O Dw- Symmetrical flashing relay (starting pulse-off) w/ retrigger/restart-2 C/O Di- Symmetrical flashing relay (starting pulse-on)-2 C/O Dit- Symmetrical flashing relay (starting pulse-on) w/ pause/summation (X1)-2 C/O Diw- Symmetrical flashing relay (starting pulse-on) w/ retrigger/restart-2 C/O H- Interval relay-2 C/O Ht- Interval relay w/ pause/summation (X1)-2 C/O Hw- Interval relay w/ retrigger/restart-2 C/O Qg- Star-delta relay (2 CO outputs w/ same common)-2 C/O Qgt- Star-delta relay (2 CO outputs w/ same common) w/ pause/summation-2 C/O Qt- Star-delta relay (2 CO outputs w/ split common)-2 C/O Qtt- Star-delta relay (2 CO outputs w/ split common) w/ pause/summation (X1)-2 C/O W- Interval relay w/ control signal off-2 C/O Wt- Interval relay w/ control signal off and pause/summation-2 C/O
Width
22.5 mm
Net weight
0.105 kg
Dielectric strength
2.5 kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation conforming to IEC 61812-1
Standards
UL 508 IEC 61812-1
Directives
2004/108/EC - electromagnetic compatibility 2006/95/EC - low voltage directive
product certifications
RCM CE EAC CSA CCC UL GL
Ambient air temperature for operation
-20…60 °C
Ambient air temperature for storage
-40…70 °C
IP degree of protection
IP40 housing: conforming to IEC 60529 IP20 terminals: conforming to IEC 60529 IP50 front panel: conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn not operating for 11 ms conforming to IEC 60068-2-27 5 gn in operation for 11 ms conforming to IEC 60068-2-27
Relative humidity
95 % at 25…55 °C
Electromagnetic compatibility
Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3 Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6 Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4 Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11 Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.6 cm
Package 1 Width
8.2 cm
Package 1 Length
9.5 cm
Package 1 Weight
116.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
40
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
5.153 kg
Unit Type of Package 3
P06
Number of Units in Package 3
640
Package 3 Height
75.0 cm
Package 3 Width
60.0 cm
Package 3 Length
80.0 cm
Package 3 Weight
74.24 kg
Warranty
18 months