RE17RMXMU

MLTFNC TMR 1C/O 24VAC/DC 240VAC

Trade Price

POA

Per

1

Unit

Pack Quantity

RE17RMXMU

Information

This Harmony RE17R timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 8A, is 17.5mm wide and can be supplied with 24V DC, 24V to 240V AC. It also has 1 changeover contact SPDT (single pole double throw). It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Multi function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Technical Specifications

Range of product

Harmony Timer Relays

Product or component type

Multifunction relay

Discrete output type

Relay

Width

17.5 mm

Device short name

RE17R

Time delay type

Ad, Ah, N, O, P, Pt, TI, Tt, W

Time delay range

6...60 s 1...10 min 0.1...1 s 1...10 h 1...10 s 6...60 min 10...100 h

Nominal output current

8 A

Contacts type and composition

1 C/O

Contacts material

Cadmium free

height

90 mm

Depth

72 mm

Control type

Selector switch front panel

[Us] rated supply voltage

24...240 V AC 50/60 Hz 24 V DC

Voltage range

0.85...1.1 Us

Supply frequency

50...60 Hz +/- 5 %

release of input voltage

10 V

Connections - terminals

Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end

Tightening torque

0.6…1 N.m conforming to IEC 60947-1

Housing material

Self-extinguishing

Repeat accuracy

+/- 0.5 % conforming to IEC 61812-1

Temperature drift

+/- 0.05 %/°C

Voltage drift

+/- 0.2 %/V

Setting accuracy of time delay

+/- 10 % of full scale at 25 °C conforming to IEC 61812-1

control signal pulse width

100 ms with load in parallel typical 30 ms typical

Insulation resistance

100 MOhm at 500 V DC conforming to IEC 60664-1

Reset time

120 ms on de-energisation typical

On-load factor

100 %

Power consumption in VA

0…32 VA at 240 V AC

Maximum power consumption in W

0.6 W at 24 V DC

Minimum switching current

10 mA at 5 V DC

Maximum switching current

8 A AC/DC

Maximum switching voltage

250 V AC

Breaking capacity

2000 VA

operating frequency

10 Hz

Electrical durability

100000 cycles (8 A at 250 V AC maximum) for resistive load

Mechanical durability

10000000 cycles

Dielectric strength

2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1

[Uimp] rated impulse withstand voltage

5 kV during 1.2/50 µs

power on delay

100 ms

Marking

CE

Creepage distance

4 kV/3 conforming to IEC 60664-1

Safety reliability data

MTTFd = 296.8 years B10d = 270000

Mounting position

Any position in relation to normal vertical mounting plane

Mounting support

35 mm DIN rail conforming to IEC 60715

Local signalling

LED indicator for on steady: relay energised, no timing in progress LED indicator for flashing: timing in progress 80 % ON and 20 % OFF LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF

Net weight

0.07 kg

Functionality

Multifunction

Compatibility code

RE17

Immunity to microbreaks

20 ms

standards

2006/95/EC 2004/108/EC IEC 61000-6-1 IEC 61000-6-4 IEC 61000-6-2 IEC 61000-6-3 IEC 61812-1

product certifications

cULus GL CSA

Ambient air temperature for storage

-30…60 °C

Ambient air temperature for operation

-20…60 °C

IP degree of protection

IP20 (terminal block) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529

Vibration resistance

20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6

Shock resistance

15 gn for 11 ms conforming to IEC 60068-2-27

Relative humidity

93 % without condensation conforming to IEC 60068-2-30

Electromagnetic compatibility

Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2 Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5 Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11 Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11 Conducted and radiated emissions: , class B, conforming to EN 55022

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.000 cm

Package 1 Width

8.300 cm

Package 1 Length

9.600 cm

Package 1 Weight

80.000 g

Unit Type of Package 2

S02

Number of Units in Package 2

40

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

3.669 kg

Warranty

18 months

Document Links

Datasheet