Trade Price
POA
Per
1
Unit
Pack Quantity
This Harmony RE17L timing relay can be set between 0.1 seconds and 100 hours, has an output rating of 0.7A, is 17.5mm wide and can be supplied with 24V to 240V AC. It also has a solid state output. It has one of market slimmest form-factors, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Range of product
Harmony Timer Relays
Product or component type
Single function relay
Discrete output type
Solid state
Width
17.5 mm
Component name
RE17L
Time delay type
C
Time delay range
10...100 h 6...60 s 6...60 min 1...10 h 1...10 s 1...10 min 0.1...1 s
Nominal output current
0.7 A
Control type
Selector switch front panel
[Us] rated supply voltage
24...240 V AC 50/60 Hz
Voltage range
0.85...1.1 Us
Supply frequency
50...60 Hz +/- 5 %
release of input voltage
7 V
control signal pulse width
0.05 s typical
Insulation resistance
100 MOhm at 500 V DC conforming to IEC 60664-1
[Uimp] rated impulse withstand voltage
5 kV during 1.2/50 µs
power on delay
100 ms
Connections - terminals
Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Tightening torque
0.6…1 N.m conforming to IEC 60947-1
Dielectric strength
2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1
Housing material
Self-extinguishing
Repeat accuracy
+/- 0.5 % conforming to IEC 61812-1
Temperature drift
+/- 0.05 %/°C
Voltage drift
+/- 0.2 %/V
Setting accuracy of time delay
+/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Reset time
350 ms on de-energisation typical
On-load factor
100 %
Power consumption in VA
0…3 VA at 240 V AC
Breaking capacity
0.5 A AC conforming to UL 0.7 A AC at 20 °C
operating frequency
10 Hz
Maximum output current
20 A
Minimum switching current
10 mA
Maximum leakage current
5 mA
Maximum switching voltage
250 V AC
Maximum voltage drop
<4 V 3-wire <8 V 2-wire
Electrical durability
100000000 cycles
Marking
CE
Creepage distance
4 kV/3 conforming to IEC 60664-1
Safety reliability data
MTTFd = 353.8 years B10d = 320000
Mounting position
Any position in relation to normal vertical mounting plane
Mounting support
35 mm DIN rail conforming to IEC 60715
Net weight
0.068 kg
Functionality
Off-delay timing
Compatibility code
RE17
Immunity to microbreaks
20 ms
Derating factor
5 mA/°C
standards
2004/108/EC IEC 61000-6-3 2006/95/EC IEC 61000-6-2 IEC 61812-1 IEC 61000-6-4 IEC 61000-6-1
product certifications
CSA GL cULus
Ambient air temperature for storage
-30…60 °C
Ambient air temperature for operation
-20…60 °C
IP degree of protection
IP20 (terminal block) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529
Vibration resistance
20 m/s² (f= 10…150 Hz) conforming to IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
Relative humidity
93 % without condensation conforming to IEC 60068-2-30
Electromagnetic compatibility
Electrostatic discharge immunity test: (in contact), level 3, 6 kV, conforming to IEC 61000-4-2 Electrostatic discharge immunity test: (in air), level 3, 8 kV, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields: (80 MHz to 1 GHz), level 3, 10 V/m, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test: (capacitive connecting clip), level 3, 1 kV, conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test: (direct), level 3, 2 kV, conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test: (differential mode), level 3, 1 kV, conforming to IEC 61000-4-5 1.2/50 µs shock waves immunity test: (common mode), level 3, 2 kV, conforming to IEC 61000-4-5 Conducted RF disturbances: (0.15...80 MHz), level 3, 10 V, conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test: (1 cycle), 0 %, conforming to IEC 61000-4-11 Voltage dips and interruptions immunity test: (25/30 cycles), 70 %, conforming to IEC 61000-4-11 Conducted and radiated emissions: , class B, conforming to EN 55022
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.7 cm
Package 1 Width
7.8 cm
Package 1 Length
9.5 cm
Package 1 Weight
71.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
40
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
3.348 kg
Warranty
18 months
Datasheet