NSYCUX3K3P4R

Cool.U.3kW 50/60Hz 400V SS Roof

Trade Price

POA

Per

1

Unit

Pack Quantity

NSYCUX3K3P4R

Technical Specifications

Range

ClimaSys

Product name

CU

Product or component type

Cooling unit

mounting type

Roof of enclosure

Installation

Indoor roof

Product destination

For enclosure

Mounting mode

By screws

Supply Voltage

400 V AC at 50/60 Hz, 3 phases

Rated Power

2900 W

Cooling power

2900 W 50/60 Hz L35-L35 2250 W 50/60 Hz L35-L50

Height

496 mm

Width

797 mm

Depth

492 mm

[In] rated current

2.5 A

Inrush current

15.7 A

Power consumption in W

1210 W at 50/60 Hz, L35-L35 1450 W at 50/60 Hz, L35-L50

Energy efficiency ratio

2.4

Control type

Electronic controller

Temperature setting range

20…50 °C

Ambient air temperature for operation

50 °C maximum: 20…46 °C inside the enclosure: 20…50 °C outside the enclosure:

Noise level

75 dB conforming to EN/ISO 3746

Pressure

25 bar

Flow rate

Internal circuit: 860 m3/h at 50/60 Hz External circuit: 3410 m3/h at 50/60 Hz

Net weight

83 kg

Cooling gas type

R134a (1.2 kg)

Type of filter

Optional external circuit filter

Protection type

Thermal protection: T 6 A Short-circuit protection (magnetic):

Material

Stainless steel

Colour

Grey (RAL 7035)

product certifications

CE

Directives

2004/108/EC - electromagnetic compatibility 2006/95/EC - low voltage directive 2006/42/EC - machinery

standards

EN 60335-1 EN 60204-1 EN 378 EN/ISO 12100 EN 60335-2-40

IP degree of protection

IP34 conforming to IEC 60529 (on the external circuit) IP54 conforming to IEC 60529 (on the internal circuit)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

49.6 cm

Package 1 Width

49.2 cm

Package 1 Length

79.7 cm

Package 1 Weight

83.0 kg

Warranty

18 months

Document Links