TPRSS080

TI SIL Starter 80 A / 37 kW

Trade Price

POA

Per

1

Unit

Pack Quantity

TPRSS080

Information

TeSys island direct SIL starter, 3 poles, 80A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 80A and motors up to 37kW@400V / 40hp@480V. In association with a TPRSM001 module and an external safety device, it can be used for safety related systems conforming to IEC 61508. It provides motor protection functions including thermal overload (setting 4-80A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys

Product name

TeSys island

Device short name

TPRSS

Product or component type

SIL motor starter

Motor starter type

Direct on line

Device presentation

Direct starter connected to an automation controller through a bus coupler Operational only when connected to a bus coupler

Function available

Upstream voltage presence detection Electrical line and load protection Power and energy monitoring when connected with TPRVM voltage module Safe stop function available when connected with a TPRSM module

Product compatibility

TPRBC bus coupler TPRVM voltage interface module TPRSM SIL interface module

Poles description

3P (3 NO)

utilisation category

AC-1 AC-2 AC-3 AC-4

Motor power kW

18.5 kW at 230 V 50 Hz (AC-3) 37 kW at 380...415 V 50 Hz (AC-3) 37 kW at 440 V 50 Hz (AC-3) 37 kW at 500 V 50 Hz (AC-3) 37 kW at 690 V 50 Hz (AC-3)

motor power HP (UL / CSA)

5 hp at 120 V AC 60 Hz for 1 phase motors 10 hp at 240 V AC 60 Hz for 1 phase motors 20 hp at 208 V AC 60 Hz for 3 phases motors 20 hp at 240 V AC 60 Hz for 3 phases motors 40 hp at 480 V AC 60 Hz for 3 phases motors 50 hp at 600 V AC 60 Hz for 3 phases motors

[Ue] rated operational voltage

<= 690 V AC 47...63 Hz

[Ie] rated operational current

66 A (at <50 °C) at <= 440 V AC-3 80 A (at <50 °C) at <= 440 V AC-1

[Ith] conventional free air thermal current

80 A (at 50 °C)

[Ui] rated insulation voltage

690 V conforming to IEC 60947-4-1 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-1

Overvoltage category

III

Thermal protection adjustment range

4…80 A

Thermal overload class

Class 5…30

Reset

Remotely or automatically

Irms rated making capacity

1000 A at 440 V conforming to IEC 60947

Rated breaking capacity

1000 A at 440 V conforming to IEC 60947

[Icw] rated short-time withstand current

900 A 40 °C - 1 s 520 A 40 °C - 10 s 260 A 40 °C - 1 min 110 A 40 °C - 10 min

Average impedance

1.5 mOhm - Ith 80 A 50 Hz

Power dissipation per pole

6.5 W AC-3 9.6 W AC-1

[Uc] control circuit voltage

24 V DC supplied by the bus coupler

Current consumption

80 mA contactor sealed 500 mA contactor closing

Power dissipation in W

21.4 W at Ie AC-3

Mechanical durability

6 Mcycles

Electrical durability

0.75 Mcycles 66 A AC-3 at Ue 440 V 0.5 Mcycles 80 A AC-1 at Ue 440 V

Maximum operating rate

3600 cyc/mn AC-3

Operating time

< 80 ms closing < 80 ms opening

Safety function

Safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module Safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module

Safety integrity level

SIL 2 conforming to IEC 61508 in single channel system architecture SILCL 2 conforming to IEC 62061 in single channel system architecture PL = d category 2 conforming to ISO 13849-1 in single channel system architecture

Safety performance level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Protection type

Thermal overload protection Motor overheat Overcurrent Undercurrent Jam Long start Stall Rapid cycle lockout Phase sequence Rapid restart lockout Phase loss Phase reversal Phase unbalance Ground current

Monitoring type

Time device ON Time device switch ON Number of faults Number of switching cycles Number of device power cycles Average current Iavg Average voltage Vavg Max current Imax Max voltage Vmax Active and reactive power with voltage module Active and reactive energy with voltage module True power factor with voltage module

Local signalling

1 LED (green/red) for DS (device status) 1 LED (green/red) for LS (load status)

Standards

EN/IEC 60947-1 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1

Product certifications

CSA CCC UL EAC

Mounting mode

Horizontal and vertical (35 mm symmetrical DIN rail)

Connections - terminals

EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) rigid EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) rigid EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) flexible without cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) flexible without cable end EverLink BTR screw connectors 1 cable(s) 1…35 mm² (AWG 16...AWG 2) flexible with cable end EverLink BTR screw connectors 2 cable(s) 1…25 mm² (AWG 16...AWG 4) flexible with cable end

Tightening torque

5 N.m - cable 1…25 mm² hexagonal 4 mm 8 N.m - cable 25…35 mm² hexagonal 4 mm

Width

55 mm

height

167 mm

Depth

125 mm

Net weight

1.248 kg

Ambient air temperature for storage

-25…70 °C

Ambient air temperature for operation

-10…50 °C without derating 50…60 °C with current derating

Relative humidity

5…95 %

Operating altitude

0...2000 m without derating

IP degree of protection

IP20

Pollution degree

2

Protective treatment

TC

Fire resistance

960 °C conforming to UL 94 850 °C conforming to IEC 60695-2-1 650 °C conforming to IEC 60695-2-12

Shock resistance

15 gn (duration = 11 ms) conforming to IEC 60068-2-27

Vibration resistance

1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6

Electromagnetic compatibility

Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4 Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 Surge immunity test (common mode), level 4, 4 kV, conforming to EN/IEC 61000-4-5 Conducted RF disturbance immunity test, 20 V, conforming to EN/IEC 61000-4-6

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6 cm

Package 1 Width

13.5 cm

Package 1 Length

17 cm

Package 1 Weight

1.32 kg

Unit Type of Package 2

S02

Number of Units in Package 2

8

Package 2 Height

15 cm

Package 2 Width

30 cm

Package 2 Length

40 cm

Package 2 Weight

10.894 kg

Warranty

18 months

Document Links

Datasheet