Trade Price
POA
Per
1
Unit
Pack Quantity
TeSys island analog IO module, 2 analog inputs, 1 analog output. Connected to a TPRBC bus coupler it is used for advanced control functions (TeSys avatars). Two analog inputs can be configured for measurement of voltage (-10/+10V, 0/+10V), current (0-20mA, 4-20mA) or temperature probes (Ni, Pt, thermocouples). One analog output can be configured for driving voltage source (-10/+10V, 0/+10V) or current source (0-20mA, 4-20mA). Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Range
TeSys
Product name
TeSys island
Device short name
TPRAN
Product or component type
Analog IO module
Device presentation
IO module providing 2 analog inputs and 1 analog output Enabling advanced control functions in a TeSys island system Operational only when connected to a bus coupler TPRBC
function of module
Measurement of voltage, current or temperature on 2 configurable analog inputs Driving voltage or current source on 1 configurable analog output
Product compatibility
TPRBC bus coupler
Analogue input number
2 isolated with common point
Analogue input type
Current 4...20 mA Current 0...20 mA Voltage 0...10 V Voltage - 10...10 V Temperature probe - 60...180 °C temperature probe: Ni 100 Temperature probe - 60...180 °C temperature probe: Ni 1000 Temperature probe -200...+850 °C temperature probe: Pt 100 Temperature probe - 200...600 °C temperature probe: Pt 1000 Thermocouple - 200...1000 °C thermocouple J Thermocouple - 200...1300 °C thermocouple K Thermocouple 0...1760 °C thermocouple R Thermocouple 0...1760 °C thermocouple S Thermocouple 0...1820 °C thermocouple B Thermocouple - 200...400 °C thermocouple T Thermocouple - 200...1300 °C thermocouple N Thermocouple - 200...800 °C thermocouple E Thermocouple 0...2315 °C thermocouple C
Measurement accuracy
+/- 0.1 % of full scale voltage 25 °C +/- 0.1 % of full scale current 25 °C +/- 0.1 % of full scale temperature probe 25 °C +/- 0.1 % of full scale in positive temperature range thermocouple 25 °C +/- 0.4 % of full scale in negative temperature range thermocouple 25 °C
Analogue input resolution
15 bits + sign full scale
Input impedance
<= 50 Ohm current >= 1 MOhm voltage >= 1 MOhm thermocouple >= 1 MOhm temperature probe
Analogue output number
1 isolated
Analogue output type
Current 4...20 mA Current 0...20 mA Voltage 0...10 V Voltage - 10...10 V
Analogue output resolution
12 bits, 4...20 mA full scale 12 bits, 0...20 mA full scale 12 bits, 0...10 V full scale 11 bits + sign, - 10...10 V full scale
Type of cable
Twisted shielded pairs cable <30 m for input/output circuit
Local signalling
1 LED (green/red) for DS (device status)
[Us] rated supply voltage
24 V DC supplied by the bus coupler
Current consumption
160 mA
Power dissipation in W
0.5 W maximum
[Uimp] rated impulse withstand voltage
0.5 kV conforming to IEC 61010-1
Standards
IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201
Product certifications
CSA UL EAC (pending)
Mounting mode
Horizontal and vertical (35 mm symmetrical rail)
Connections - terminals
Input/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) rigid Input/output circuit: removable spring terminal block 8 cable(s) 0.2…2.5 mm² (AWG 24...AWG 14) flexible without cable end Input/output circuit: removable spring terminal block 8 cable(s) 0.25…2.5 mm² (AWG 22...AWG 14) flexible with cable end
Width
25 mm
height
118 mm
Depth
114 mm
Net weight
0.172 kg
Ambient air temperature for storage
-25…70 °C
Ambient air temperature for operation
-10…60 °C
Relative humidity
5…95 %
Operating altitude
0...2000 m without derating
IP degree of protection
IP20
Pollution degree
2
Protective treatment
TC
Fire resistance
960 °C conforming to UL 94
Shock resistance
15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration resistance
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic compatibility
Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 Radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 Fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4 Surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.5 cm
Package 1 Width
13.5 cm
Package 1 Length
15.5 cm
Package 1 Weight
251.0 g
Unit Type of Package 2
S03
Number of Units in Package 2
16
Package 2 Height
30.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
4.793 kg
Warranty
18 months