XPSMCMER0004

4 safety relays unit 4NO+2NC

Trade Price

£239.07

Per

1

Unit

EA

Pack Quantity

1

XPSMCMER0004

Information

This Modicon MCM safe relay output expansion module has 4 guided contact safety relay outputs (2 NO + 1 NC) for 2 independent outputs, 2 start/restart interlock inputs and is fitted with captive screw clamp terminals. It is designed to monitor safety actuators for relay outputs, with a rated supply voltage of 24V DC and a maximum power dissipation of 3W. It is furnished with screw clamp terminals, removable terminal block for electrical connection. It is an IP20 rated product. The safe relay modules type XPSMCMER0004 use guided contact safety relays, each of which provides two N.O. contacts and one N.C. contact in addition to the N.C. feedback contact. This safe relay output expansion module figures LEDs on its front face, displaying the status (power supply, run, internal or external errors, inputs status, restart signal, output channels). The safe relay output modules type XPSMCMER0002 and XPSMCMER0004 do not require the backplane expansion connectors as they are directly wired to the selected OSSD. It weighs 0.3kg. Its dimension are 22.5mm (Depth), 99mm (Height) and 114.5mm (Width). Its housing is red. It is powered with 24 VDC. It is ideal for monitoring safety functions such as emergency stop, guard monitoring, perimeter guarding, position monitoring, speed monitoring and enabling movement. The safe controller CPU Modicon MCM are certified by TüV SÜD meeting the industrial safety standards of Category 4, PL e according to EN/ISO 13849-1 and SILCL 3 according to IEC/EN 61508 and IEC/EN 60261. Compatible accessory for safe relay output module is a memory card. The module instals on Omega 35mm DIN rail conforming to EN 50022. The Modicon MCM modular safety controller system provide flexibility and scalability from 8 inputs, 2 dual/4 single channel outputs up to 128 inputs, 16 dual/32 single channel outputs, up to 32 or 48 diagnostic status outputs. Modicon MCM modular safety controller system are designed to monitor multiple safety functions on and around a machine to minimise the risk of people accessing the dangerous moving parts of the machine.

Technical Specifications

Range of product

Preventa Safety automation

Product or component type

Safe relay output module

Device short name

XPSMCM

Electrical connection

Screw terminal

[Us] rated supply voltage

24 V - 20...20 % DC

Number of outputs

4 relay

Function of module

Monitoring safety actuators for relay output

Maximum power dissipation in W

3 W

Integrated connection type

Not connected to backplane expansion bus

Switching voltage

10 V DC

Associated fuse rating

3.5 A, slow-blow

Safety level

Can reach category 4 conforming to EN/ISO 13849-1 Can reach PL = e conforming to EN/ISO 13849-1 Can reach SIL 3 conforming to EN/IEC 61508 SILCL 3 conforming to IEC 62061

Quality labels

CE

Output type

Relay, 4 NO + 2 NC circuit(s), volt-free

Quantity per set

1

Switching time

12 ms

Maximum switching voltage

400 V AC 250 V DC

Minimum switching current

20 mA

Maximum switching current

6 A

Number of terminal blocks

6

Local signalling

1 LED green with PWR marking for power ON 1 LED green with RUN marking for RUN (status) 1 LED red with E IN marking for internal error 1 LED red with E EX marking for external error 2 LEDs orange with ADDR marking for node address 2 LEDs green/red with RELAY K1...K2 marking for relay contact

Connections - terminals

2 captive screw clamp terminals, removable terminal block 1 captive screw clamp terminals, removable terminal block

Cable cross section

0.2…1.5 mm² - AWG 24...AWG 16 flexible cablewithout cable end 0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end 0.25…1 mm² - AWG 23...AWG 18 flexible cablewith cable end, without bezel 0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel 0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, without bezel 0.5…1.5 mm² - AWG 20...AWG 16 flexible cablewith cable end, with double bezel 0.2…1 mm² - AWG 24...AWG 18 solid cablewithout cable end 0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end

Mounting support

Omega 35 mm DIN rail conforming to EN 50022

Width

22.5 mm

height

99 mm

Depth

114.5 mm

Net weight

0.3 kg

standards

IEC 62061 EN/ISO 13849-1 EN/IEC 61800-5-1 EN/IEC 61508

product certifications

RCM cULus TÜV

IP degree of protection

IP20

Ambient air temperature for operation

-10…55 °C

Ambient air temperature for storage

-20…85 °C

Relative humidity

10…95 %

Pollution degree

2

[Uimp] rated impulse withstand voltage

4 kV conforming to EN/IEC 61800-5-1

Safety reliability data

B10d = 300000 utilisation category AC-15 230 V, , <3 A conforming to EN/ISO 13849-1 B10d = 750000 utilisation category AC-15 230 V, , <1 A conforming to EN/ISO 13849-1 B10d = 10000000 utilisation category DC-13 24 V, , <2 A conforming to EN/ISO 13849-1

Insulation

250 V AC between power supply and housing conforming to EN/IEC 61800-5-1

Overvoltage category

II

Electromagnetic compatibility

Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to EN/IEC 61000-4-2 Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to EN/IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to EN/IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3

Vibration resistance

+/-0.35 mm (f= 10…55 Hz) conforming to EN/IEC 61496-1

Shock resistance

10 gn for 16 ms (1000 shocks on each axis) conforming to EN/IEC 61496-1

Electrical durability

20000000 cycles

Mechanical durability

20000000 cycles

Service life

20 year(s)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

4.6 cm

Package 1 Width

12.4 cm

Package 1 Length

16.2 cm

Package 1 Weight

305.0 g

Unit Type of Package 2

S01

Number of Units in Package 2

6

Package 2 Height

15.0 cm

Package 2 Width

15.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

2.07 kg

Warranty

18 months

Document Links