ABLS1A24031

POW.SUP. 24V 3.1A 1PH OPT

Trade Price

£123.66

Per

1

Unit

EA

Pack Quantity

1

ABLS1A24031

Information

This ABLS regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC and 140 V to 340 V DC, a rated output current of 3,13A at 24V DC and a rated power output of 75W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. It installs on omega rail or fixing by screw. Its width is 27mm, its height is 123,6mm, its depth is 102mm. It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected. It weighs 0.220kg. It is a power supply for industrial use, rail mounting. It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme. The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 10A, C curve or 13A, B-curve. It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation. Thanks to its book housing, it can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness.

Technical Specifications

Range of product

Modicon Power Supply

Product or component type

Power supply

Power supply type

Regulated switch mode

Variant option

Optimized

Enclosure material

Plastic

Nominal input voltage

100...240 V AC single phase 100...240 V AC phase to phase 140...340 V DC

Rated power in W

75 W

Output voltage

24 V DC

Power supply output current

3.13 A

Input voltage limits

85...264 V AC without temperature derating 120...375 V DC without temperature derating 85…120 V DC with temperature derating

Nominal network frequency

50…60 Hz

Network system compatibility

TN TT IT

Maximum leakage current

1 mA 240 V AC

Input protection type

Integrated fuse (not interchangeable) 5 A External protection (recommended) 20 A Curve C External protection (recommended) 13 A Curve B External protection (recommended) 10 A Curve C

Inrush current

40.0 A at 115 V 80.0 A at 230 V

Power factor

0.55 at 115 V AC 0.45 at 230 V AC

Efficiency

88 % at 230 V AC

Output voltage adjustment

21.6...26.4 V

Power dissipation in W

15 W

Current consumption

< 1.8 A 115 V AC < 1 A 230 V AC < 0.8 A 140 V DC

Turn-on time

< 1.2 s

Holding time

> 20 ms 115 V AC > 40 ms 230 V AC

Startup with capacitive loads

5000 µF

Residual ripple

< 120 mV

Meantime between failure [MTBF]

700000 h at 25 °C, full load conforming to SR 332

Output protection type

Against overload and short-circuits, protection technology: automatic reset Against over temperature, protection technology: manual reset Against overvoltage, protection technology: manual reset

Connections - terminals

Screw connection: 0.5...2.5 mm², (AWG 20...AWG 14) for output Screw connection: 0.75...2.5 mm², (AWG 18...AWG 14) for input

Line and load regulation

< 0.5 % at 0 to 100 % load at 25 °C < 1 % at full voltage range in line at 25 °C

Status LED

1 LED (green) output voltage

Depth

102 mm

height

123.6 mm

Width

27 mm

Net weight

0.22 kg

Output coupling

Parallel Serial

Mounting support

Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Double-profile DIN rail

Supply

SELV conforming to EN/IEC 60950-1 SELV conforming to EN/IEC 60204-1 SELV conforming to IEC 60364-4-41

Dielectric strength

3000 V AC with input to output

Service life

10 year(s)

Overvoltage category

II

standards

EN 62368-1 EN/IEC 61010-1 EN 61010-2-201 EN/IEC 61204-3 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61000-3-2 EN 61000-3-3 UL 62368-1 UL 61010-1 UL 61010-2-201 CSA C22.2 No 62368-1 CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 EN/IEC 62368-1

Product certifications

CE CUL listed CUL recognized RCM CB Scheme EAC KC NEC: class 2

Operating altitude

< 5000 m

Shock resistance

150 m/s² for 11 ms

IP degree of protection

IP20

Ambient air temperature for operation

-20…-10 °C with current derating of 1 % per °C mounting position A < 2000 m -10…40 °C without derating mounting position A 115 V AC < 2000 m -10…50 °C without derating mounting position A 230 V AC < 2000 m 40…70 °C with current derating of 1.67 % per °C mounting position A 115 V AC < 2000 m 50…70 °C with current derating of 2.5 % per °C mounting position A 230 V AC < 2000 m

Electrical shock protection class

Class I

Pollution degree

2

Vibration resistance

3 mm (f= 2…9 Hz) conforming to IEC 60068-2-6 10 m/s² (f= 9…200 Hz) conforming to IEC 60068-2-6

Electromagnetic immunity

Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to EN/IEC 61000-4-2 Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to EN/IEC 61000-4-2 Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3 Immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4 Surge immunity test - test level: 4 kV (between power supply and earth) conforming to EN/IEC 61000-4-5 Surge immunity test - test level: 3 kV (between phases) conforming to EN/IEC 61000-4-5 Immunity to conducted RF disturbances - test level: 15 V (0.15...80 MHz) conforming to EN/IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8 Immunity to voltage dips conforming to EN/IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to EN 61000-3-2 conforming to EN 55016-1-2 conforming to EN 55016-2-1

Electromagnetic emission

Conducted emissions conforming to EN 61000-6-3 Radiated emissions conforming to EN 61000-6-4

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.7 cm

Package 1 Width

14.0 cm

Package 1 Length

16.0 cm

Package 1 Weight

303.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

22

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

7.283 kg

Unit Type of Package 3

P12

Number of Units in Package 3

528

Package 3 Height

105.0 cm

Package 3 Width

80.0 cm

Package 3 Length

120.0 cm

Package 3 Weight

192.6 kg

Warranty

18 months

Document Links