METSEPM5100

PM5100 power meter 1DO

Trade Price

£267.28

Per

1

Unit

EA

Pack Quantity

1

METSEPM5100

Information

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication is pulse output only. The meter also has 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).

Technical Specifications

Range

PowerLogic

Product name

PowerLogic PM5000

Device short name

PM5100

Product or component type

Power meter

Power quality analysis

up to the 15th harmonic

Device application

Power monitoring

Type of measurement

Current Voltage Frequency Power factor Energy Active and reactive power

supply voltage

90...450 V AC 45...65 Hz 100...300 V DC

Network frequency

60 Hz 50 Hz

[In] rated current

5 A 1 A

type of network

3P + N 1P + N 3P

Maximum power consumption in VA

11 VA at 415 V

Ride-through time

80 ms 120 V AC typical 100 ms 230 V AC typical 100 ms 415 V AC typical 50 ms 125 V DC typical

Display type

Monochrome graphic LCD

Display resolution

128 x 128 pixels

Sampling rate

64 samples/cycle

Measurement current

50…8500 mA

Analogue input type

Voltage (impedance 5 MOhm) Current (impedance <= 0.3 mOhm)

Measurement voltage

35…760 V AC 45...65 Hz between phases 20…400 V AC 45...65 Hz between phase and neutral

Frequency measurement range

45…65 Hz

Number of inputs

0

Measurement accuracy

Active energy +/- 0.5 % Reactive energy +/- 2 % Active power +/- 0.5 % Apparent power +/- 0.5 % Frequency +/- 0.05 % Power factor +/- 0.5 Current +/- 0.5 % Voltage +/- 0.5 % Apparent energy +/- 0.5 % Reactive power +/- 2 %

Accuracy class

Class 0.5S active energy conforming to IEC 62053-22

Number of outputs

1 pulse (energy)

Communication port protocol

-

Communication port support

-

data recording

Min/max of instantaneous values Time stamping

Connections - terminals

Voltage circuit: screw terminal block4 Control circuit: screw terminal block2 Current transformer: screw terminal block6 Input/output circuit: screw terminal block6 RS485 link: screw terminal block4

Mounting mode

Flush-mounted

Mounting support

Framework

standards

EN 50470-1 IEC 62053-22 UL 61010-1 IEC 62053-24 IEC 61557-12 EN 50470-3 IEC 60529

Product certifications

CE conforming to IEC 61010-1 CULus conforming to UL 61010-1

Width

96 mm

Depth

72 mm

height

96 mm

Net weight

380 g

Electromagnetic compatibility

Limits for harmonic current emissions class A conforming to IEC 61000-3-2 Electrostatic discharge level 4 conforming to IEC 61000-4-2 Conducted RF disturbances level 3 conforming to IEC 61000-4-6 Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 Conducted and radiated emissions class B conforming to EN 55022 Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 Surge immunity test conforming to IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

IP degree of protection

IP54 display: conforming to IEC 60529 IP30 rear: conforming to IEC 60529

Relative humidity

5…95 % at 50 °C non-condensing

Pollution degree

2

Ambient air temperature for operation

-25…70 °C meter -20…70 °C display -25…-20 °C (with reduced performance) display

Ambient air temperature for storage

-40…85 °C

Operating altitude

2000 m CAT III

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

11.0 cm

Package 1 Width

12.6 cm

Package 1 Length

12.6 cm

Package 1 Weight

550.0 g

Unit Type of Package 2

S03

Number of Units in Package 2

12

Package 2 Height

30.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

6.54 kg

Unit Type of Package 3

P06

Number of Units in Package 3

96

Package 3 Height

50.0 cm

Package 3 Width

80.0 cm

Package 3 Length

60.0 cm

Package 3 Weight

61.44 kg

Warranty

18 months

Document Links