RUMC22JD

2CO 10A RELAY CYL 12DC

Trade Price

POA

Per

1

Unit

Pack Quantity

RUMC22JD

Information

This Harmony RUM universal plug-in relay uses cylindrical pins, has a control coil voltage of 12V DC and has 2 changeover contacts double pole double throw with a rating of 10A." "It provides a complete system solution for the most demanding applications." "It also offers one-step lockable test button and “Power On” LED for readiness." "It helps to reduce the size of enclosures and increase machine reliability, you can mount nearly everywhere." "The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts." "Workability for hard-wired logic automated systems to complement the functions of industrial programmable logic controllers (PLCs)." "Status display with LED, clearly signal both in the day and night." 0 0 0 0 0 0 0 0 0

Technical Specifications

Range of product

Harmony Electromechanical Relays

Series name

Universal

Product or component type

Plug-in relay

Device short name

RUM

Contacts type and composition

2 C/O

[Uc] control circuit voltage

12 V DC

[Ithe] conventional enclosed thermal current

10 A at -40…55 °C

Status LED

With

Control type

Lockable test button

Utilisation coefficient

20 %

Shape of pin

Cylindrical

[Ui] rated insulation voltage

250 V conforming to IEC 300 V conforming to CSA 300 V conforming to UL

[Uimp] rated impulse withstand voltage

4 kV (1.2/50 µs)

Contacts material

AgNi

[Ie] rated operational current

10 A at 277 V AC conforming to UL 10 A at 30 V DC conforming to UL 10 A at 30 V DC conforming to CSA 5 A at 250 V AC (NC) conforming to IEC 5 A at 28 V DC (NC) conforming to IEC 10 A at 250 V AC (NO) conforming to IEC 10 A at 28 V DC (NO) conforming to IEC 10 A at 277 V AC conforming to CSA

Maximum switching voltage

250 V conforming to IEC

Resistive rated load

10 A at 250 V AC 10 A at 28 V DC

Maximum switching capacity

2500 VA/280 W

Minimum switching capacity

170 mW at 10 mA, 17 V

Operating rate

<= 18000 cycles/hour no-load <= 1200 cycles/hour under load

Mechanical durability

5000000 cycles

Electrical durability

100000 cycles for resistive load

Average coil consumption in W

1.4 W

Drop-out voltage threshold

>= 0.1 Uc DC

Operate time

20 ms at nominal voltage

Release time

20 ms at nominal voltage

Average coil resistance

120 Ohm at 20 °C +/- 15 %

Rated operational voltage limits

9.6...13.2 V DC

Protection category

RT I

Test levels

Level A group mounting

Safety reliability data

B10d = 100000

Operating position

Any position

Net weight

0.086 kg

Device presentation

Complete product

Dielectric strength

1500 V AC between contacts with micro disconnection 2500 V AC between coil and contact with reinforced 2000 V AC between poles with basic

product certifications

CSA UL EAC

standards

UL 508 CSA C22.2 No 14 IEC 61810-1

Ambient air temperature for storage

-40…85 °C

Ambient air temperature for operation

-40…55 °C

Vibration resistance

3 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles in operation 4 gn, amplitude = +/- 1 mm (f = 10…150 Hz)5 cycles not operating

IP degree of protection

IP40

Shock resistance

10 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27 10 gn (duration = 11 ms) for not operating conforming to IEC 60068-2-27

Pollution degree

3

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

3.6 cm

Package 1 Width

3.5 cm

Package 1 Length

6.9 cm

Package 1 Weight

85 g

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Height

4 cm

Package 2 Width

14.6 cm

Package 2 Length

20 cm

Package 2 Weight

939 g

Unit Type of Package 3

S02

Number of Units in Package 3

60

Package 3 Height

15 cm

Package 3 Width

30 cm

Package 3 Length

40 cm

Package 3 Weight

6.244 kg

Warranty

18 months