Trade Price
POA
Per
1
Unit
Pack Quantity
Range of product
Harmony Solid State Relays
Product or component type
Solid state relay up to 75 A
Provided accessory
Thermal pad
Device short name
SSP1
mounting support
Panel
Number of phases
1 phase
[In] rated current
75 A
solid state output type
Zero voltage switching SCR output
Output switching mode
Zero voltage switching
[Uc] control circuit voltage
4...32 V DC
Minimum switching voltage
4 V DC turn-on
Maximum switching voltage
1 V DC turn-off
Response time
0.5 cycle (turn-on) 0.5 cycle (turn-off)
Input current
7…12 mA
Output voltage
48...660 V AC
Load current
0.15…75 A
Transient overvoltage
1200 V
Surge current
1000 A for 16.6 ms
Maximum I²t for fusing
4150 A².s for 8.33 ms at 60 Hz 4555 A².s for 10 ms at 50 Hz
Co-ordination type
Type 1 - 50 A miniature circuit breaker (MCB) - curve B Type 2 - 40 A miniature circuit breaker (MCB) - curve B
Maximum leakage current
1 mA off-state
Maximum voltage drop
<1.15 V on-state
DV/dt
500 V/µs off-state at maximum voltage
Power factor
0.5 (with maximum load)
Motor controller rating
1.5 hp 120 V AC 3 hp 240 V AC 7.5 hp 480 V AC
Insulation resistance
1000 MOhm at 500 V DC
Maximum capacitance
8 pF for input/output
Dielectric strength
4 kV AC for input/output 4 kV AC for input or output to case
[Uimp] rated impulse withstand voltage
6 kV output to case 6 kV input to output
Tightening torque
1.5...1.7 N.m for input 2...2.2 N.m for output 17.7...19.47 lb.in for output 13.27...15.04 lb.in for input 0.5...0.6 N.m for auxillary terminal 4.4...5.3 lb.in for auxillary terminal
Connections - terminals
Screw terminals: 0.2...3.3 mm², (AWG 24...AWG 12) with cable end for input Screw terminals: 0.5...5.26 mm², (AWG 20...AWG 10) with cable end for output Screw terminals: 0.2...3.3 mm², (AWG 24...AWG 12) without cable end for input Screw terminals: 0.5...8.26 mm², (AWG 20...AWG 8) without cable end for output Forked type tag connectors: 9.2 x 4 mm for input Ring lugs: 9.2 x 4 mm for input Forked type tag connectors: 11.7 x 4.5 mm for output Ring lugs: 11.7 x 4.5 mm for output
Auxiliary/Alarm connection terminal
Screw-type connector, 0.5...1.5 mm² (AWG 20...AWG 16) with slotted Philips screwdriver
Thermal resistance
0.3 °C/W junction to case
LED indicator
LED, steady, green for ON status for control input/test button actuated LED, steady, amber for ON status for load LED, flashing, amber for control input to energise load LED, steady, red for open-circuit for control input LED, flashing, red for load cut-off/short-circuit
Maximum alarm output current
30 mA at 32 V DC
minimum load current
150 mA
IP degree of protection
IP20
Electromagnetic compatibility
Electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2 Electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test criteria A output ports conforming to IEC 61000-4-3 Radiated radio-frequency electromagnetic field immunity test criteria B alarm port conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4 Surge immunity test 1 kV criteria A output ports line to line conforming to IEC 61000-4-5 Surge immunity test 2 kV criteria A output ports line to earth conforming to IEC 61000-4-5
Safety reliability data
B10d = 1731395 MTTFd = 1875.9 years
Net weight
97.1 g
Device presentation
Complete product
Ambient air temperature for operation
-40…80 °C
Ambient air temperature for storage
-40…125 °C
Pollution degree
2
Overvoltage category
III
product certifications
CSA EAC UL CE
Marking
CSA UL EAC CE
standards
UL 508 IEC 60950-1 IEC 62314 CSA C22.2 No 14-13
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
4.600 cm
Package 1 Width
4.500 cm
Package 1 Length
5.900 cm
Package 1 Weight
110.000 g
Unit Type of Package 2
S01
Number of Units in Package 2
28
Package 2 Height
15.000 cm
Package 2 Width
15.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
3.470 kg
Warranty
18 months
Datasheet