Trade Price
£2,383.86
Per
1
Unit
EA
Pack Quantity
1
Micrologic 6.0E (Energy meter) is an electronic control unit used on Compact NS630b to NS3200 fixed circuit breakers. This control unit has a selective and earth fault protection (LSIG) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 6.0E offers an adjustable earth fault protection. Micrologic 6.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 6.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with fixed Compact NS basic frame.
Range
ComPact
Range of product
ComPact NS630b...1600 ComPact NS1600b...3200
Product or component type
Trip unit
Trip unit name
MicroLogic 6.0 E
Trip unit technology
Electronic
Range compatibility
ComPact NS1600b...3200 ComPact NS630b...1600
Device application
Distribution
Number of poles
4P 3P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Selective + earth-fault protection
Protection type
for overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Trip unit rating
630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Fixed
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5...10 x Ir
Short-time protection delay adjustment type tsd
Adjustable
[tsd] Short-time protection delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
Off 2...15 x In
Ground-fault protection pick-up adjustment type Ig
Adjustable 9 settings
[Ig] ground-fault protection pick-up adjustment range
0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A
Ground-fault protection time delay adjustment type tg
Adjustable
[tg] ground-fault protection time delay adjustment range
0…0.4 s I²t=off 0.1…0.4 s I²t=on
earth-leakage protection
Without
Zone selective interlocking ZSI
With
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Energy meter
communication of data
Measurement readout Protection and alarm settings
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.8 cm
Package 1 Width
8.0 cm
Package 1 Length
21.5 cm
Package 1 Weight
272.0 g
Warranty
18 months
Datasheet