LV426950

OF/SD Contact NSXm PP-B

Trade Price

POA

Per

1

Unit

Pack Quantity

LV426950

Information

It is a single standard auxiliary contact that provides two remote information of the circuit breaker status. It is used on Compact NSXm and PowerPact B devices. The OF contact (open/closed) indicates the position of the circuit breaker main contacts. The SD contact (trip indication) indicates if the circuit breaker has tripped. There is one auxiliary contact model for OF and SD information, depending on where it is fitted in the device. This auxiliary is a common point changeover type contact with 1 normally open contact and 1 normally closed contact. The rated current is 5A and the minimum load is 2mA at 17 VDC. Utilization categories are AC12/AC13/DC12/DC13/DC14. Compact NSXm embeds 2 auxiliary contacts and their presence is visible on the front face through green flags. It complies with IEC 60947-5-1 standard.

Technical Specifications

Product or component type

Auxiliary contact

Device short name

SD OF

Device application

Breaker status monitoring

Range compatibility

PowerPact (PowerPact B) ComPact (ComPact NSXm)

Signal contacts composition

1 NO/NC

fault type

Overload Short-circuit

Local signalling

ON/OFF indication for open/close Trip indicator for relay trip indicator

auxiliary contacts type

Standard

Mounting mode

Clip-on

[Ith] conventional free air thermal current

5 A

Breaking capacity (A)

AC-12: 5 A at 24 V AC 50/60 Hz AC-12: 5 A at 48 V AC 50/60 Hz AC-12: 5 A at 110...127 V AC 50/60 Hz AC-12: 5 A at 220/240 V AC 50/60 Hz AC-12: 5 A at 380/440 V AC 50/60 Hz AC-12: 5 A at 660/690 V AC 50/60 Hz AC-15: 5 A at 24 V AC 50/60 Hz AC-15: 5 A at 48 V AC 50/60 Hz AC-15: 4 A at 110...127 V AC 50/60 Hz AC-15: 3 A at 220/240 V AC 50/60 Hz AC-15: 2.5 A at 380/440 V AC 50/60 Hz AC-15: 0.1 A at 660/690 V AC 50/60 Hz DC-12: 5 A at 24 V DC 50/60 Hz DC-12: 2.5 A at 48 V DC 50/60 Hz DC-12: 0.6 A at 110 V DC 50/60 Hz DC-12: 0.3 A at 250 V DC DC-13: 2.5 A at 24 V DC DC-13: 1.2 A at 48 V DC DC-13: 0.35 A at 110 V DC DC-13: 0.05 A at 250 V DC DC-14: 1 A at 24 V DC DC-14: 0.2 A at 48 V DC DC-14: 0.05 A at 110 V DC DC-14: 0.03 A at 250 V DC

Minimum load

2 mA at 17 V DC

Auxiliary connection terminal

Spring

Wire stripping length

8 mm for front connection

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

1.200 cm

Package 1 Width

7.500 cm

Package 1 Length

10.500 cm

Package 1 Weight

25.000 g

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Height

5.000 cm

Package 2 Width

14.000 cm

Package 2 Length

25.000 cm

Package 2 Weight

257.000 g

Unit Type of Package 3

S03

Number of Units in Package 3

220

Package 3 Height

30.000 cm

Package 3 Width

30.000 cm

Package 3 Length

40.000 cm

Package 3 Weight

6.300 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet