M9R84491

M9 GFP 4P 100A 260MA A-SI 480Y/

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

M9R84491

Information

This is a Multi GFP residual current circuit breaker (RCCB). It is a 4P circuit breaker with In rated current of 100A, A-SI type protection class and a 260mA earth leakage sensitivity. It protects persons against electric shock by direct contact. It also protects installations against fire risks. The tripping upon fault is indicated by a red mechanical status indicator on the front panel. The A-SI type offers enhanced immunity to electrical disturbances. This product is dedicated to original equipment manufacturers (OEM) and control panel builders in indisutrial and tertiary buildings. It is compliant with IEC/EN 61008-1 standard. The (Im/IΔm) rated breaking and making short circuit capacity is 1500A. The (Inc/IΔc) conditional rated short circuit current is 10kA. It has a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 440VAC. The Uimp rated impulse withstand voltage is 6kV. The frequency is 50Hz or 60Hz. It is DIN rail mountable. The width in 9mm pitches is 8. The product colour is light grey (RAL7035). The dimensions are (W) 72mm x (H) 81mm x (D) 60mm. The weight is 0.45kg. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 70°C.

Technical Specifications

Range

Multi9

Product name

Multi9 GFP

Product or component type

Residual current circuit breaker (RCCB)

Device short name

GFP

Device application

Distribution

Poles description

4P

Neutral position

Left

[In] rated current

100 A at 40 °C conforming to EN/IEC 61008-1

Network type

AC

Earth-leakage sensitivity

260 mA conforming to UL 1053 300 mA conforming to EN/IEC 61008-1

earth-leakage protection time delay

Instantaneous

Earth-leakage protection class

Type A-SI (Super Immunised)

Utilisation category

AC-23A conforming to EN/IEC 61008-1

Network frequency

50/60 Hz

[Ue] rated operational voltage

415 V AC 50 Hz 480Y/277 V AC 60 Hz

Residual current tripping technology

Voltage independent

Rated breaking and making capacity

Idm 1500 A conforming to EN/IEC 61008-1

Rated conditional short-circuit current

Inc 10 kA 100 A gG

[Ui] rated insulation voltage

440 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage

6 kV conforming to EN/IEC 61008-1

Contact position indicator

Yes

Control type

Toggle

Local signalling

ON, OFF, fault trip

Mounting mode

Clip-on

mounting support

DIN rail

9 mm pitches

8

height

81 mm

Width

72 mm

Depth

60 mm

Net weight

0.45 kg

Colour

Grey

Mechanical durability

20000 cycles

Locking options description

Padlocking in OFF position

Connections - terminals

Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible Tunnel type terminals (top or bottom) 1…35 mm² (AWG 18...AWG 2) - rigid Tunnel type terminals (top or bottom) 1…25 mm² (AWG 18...AWG 3) - flexible with ferrule

Wire stripping length

14 mm for top or bottom connection

Tightening torque

3.5 N.m top or bottom

Standards

EN/IEC 61008-1 UL 1053

Product certifications

IEC UL

IP degree of protection

IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529

Pollution degree

3

Electromagnetic compatibility

8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61008-1

Tropicalisation

2 conforming to IEC 60068-1

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-25…60 °C

Ambient air temperature for storage

-40…70 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

9.200 cm

Package 1 Width

7.700 cm

Package 1 Length

8.500 cm

Package 1 Weight

340.000 g

Unit Type of Package 2

S03

Number of Units in Package 2

27

Package 2 Height

30.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

9.640 kg

Warranty

18 months