KTA1000DB410

KT 4X1000AL EXPANSION UNIT

Trade Price

POA

Per

1

Unit

Pack Quantity

KTA1000DB410

Technical Specifications

Range

Canalis

Product name

KT

Product or component type

Expansion unit

Busbar description

Flexible bar

Device short name

KTA

Device application

Feeder length

Material

Aluminium

[Ie] rated operational current

1000 A at 35 °C

polarity

3L + N + PE

Number of tap-off outlets

0

Length

1000 mm

provided equipment

Trunking unit Jointing unit

Housing material

Polyester film

Contacts material

Copper

[Ue] rated operational voltage

1000 V

Network frequency

50/60 Hz

[Ui] rated insulation voltage

1000 V

[Icw] rated short-time withstand current

50 kA

[Ipk] rated peak withstand current

110 kA

Radiated magnetic field

0.5 µT

Thermal stress limit

2500000 kA².s

THDI

0…15 % 1000 A 15…33 % 1250 A 33…100 % 1600 A

Maximum voltage drop

<0.006 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.006 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.0056 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.0052 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Mounting mode

By hook

mounting support

Cantilever arm Pendant

Installation direction

Vertical Horizontal

Horizontal distance

30 m

Neutral position

Right

Standards

IEC 61439-1 IEC 61439-6

Dimension type

Fix

Width

140 mm

height

104 mm

Colour

White (RAL 9001)

Net weight

16 kg

Linear load

16 kg/m

IP degree of protection

IP55 conforming to IEC 60529

IK degree of protection

IK08 conforming to IEC 62262

derating factor

0…35 °C (100 % of In) 35…40 °C (97 % of In) 40…45 °C (93 % of In) 45…50 °C (90 % of In) 50…55 °C (86 % of In)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

14.0 cm

Package 1 Width

100.0 cm

Package 1 Length

15.0 cm

Package 1 Weight

17.0 kg

Warranty

18 months

Document Links

Datasheet