33070

MICROLOGIC 5.0

Trade Price

POA

Per

1

Unit

Pack Quantity

33070

Technical Specifications

Product or component type

Control unit

Trip unit name

MicroLogic 5.0

Trip unit technology

Electronic

Range compatibility

MasterPact NT MasterPact NW Compact NS Masterpact MT PowerPact P-Frame PowerPact R-Frame

Device application

Distribution

Number of poles

4P 3P

Protected poles description

3t 3t + N/2 4t

Trip unit protection functions

Selective protection

Protection type

for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection

Trip unit rating

630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Fixed Drawout

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.5…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

2...15 x In Off

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-50…85 °C

Warranty

18 months

Document Links

Datasheet