48358

Micrologic 2.0 A Drawout NW

Trade Price

POA

Per

1

Unit

Pack Quantity

48358

Technical Specifications

Range

MasterPact

Range of product

MasterPact NW

Product or component type

Control unit

Trip unit name

MicroLogic 2.0 A

Trip unit technology

Electronic

Range compatibility

Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection

Device application

Distribution

Number of poles

3P 4P

Protected poles description

4t 3t 3t + N/2

Trip unit protection functions

Basic protection

Protection type

for overload protection (long time) for instantaneous short-circuit protection

Trip unit rating

800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Drawout

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

1.5...10 x Ir

earth-leakage protection

Without

Zone selective interlocking ZSI

Without

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type

Digital display

Type of measurement

Ammeter

communication of data

Measurement readout Protection and alarm settings

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.8 cm

Package 1 Width

8.0 cm

Package 1 Length

21.5 cm

Package 1 Weight

366.0 g

Warranty

18 months

Document Links

Catalogue page

Datasheet