Trade Price
POA
Per
1
Unit
Pack Quantity
This Harmony RM22-LG relay allows monitoring of liquid level control in 3-phase networks. This modular multi function 3-phase liquid level control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slim form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
Range of product
Harmony Control Relays
Product or component type
Level control relay
Relay type
Level control relay
Relay name
RM22L
Relay monitored parameters
Detection by resistive probes
time delay
Without
Switching capacity in VA
2000 VA
Minimum switching current
10 mA at 5 V DC
Maximum switching current
8 A AC
Utilisation category
AC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1
Contacts type and composition
2 C/O
Maximum switching voltage
250 V AC
[Un] rated nominal voltage
24...240 V AC/DC 50/60 Hz
Supply voltage limits
20.4…264 V AC/DC
power consumption
1.5 W DC
Output contacts
2 C/O
Nominal output current
8 A
delay at power up
0.6 s
Maximum electrode voltage
12 V AC
Maximum electrode current
1 mA
Repeat accuracy
+/- 2 % for time delay
Measurement error
< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
Maximum cable distance between devices
1000 m between probe and delay
Sensitivity scale
5...100 kOhm St (Standard Sensitivity)
Sensitivity adjustment
5…100 %
Maximum supply current for sensors
1 mA
Cable capacitance
1 nF at HS (High Sensitivity) for probe cable 2.2 nF at St (Standard Sensitivity) for probe cable 4.7 nF at LS (Low Sensitivity) for probe cable
Overvoltage category
III conforming to IEC 60664-1
insulation
Between supply and measurement
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Tightening torque
0.6…1 N.m conforming to IEC 60947-1
Housing material
Self-extinguishing plastic
Mounting support
35 mm DIN rail conforming to IEC 60715
Mounting position
Any position
Electrical durability
100000 cycles
Mechanical durability
10000000 cycles
Contacts material
Cadmium free
Safety reliability data
B10d = 120000 MTTFd = 125.5 years
Width
22.5 mm
Net weight
0.1 kg
Immunity to microbreaks
100 ms DC 90 ms AC
Electromagnetic compatibility
Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1 Immunity for industrial environments conforming to IEC 61000-6-2 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Emission standard for industrial environments conforming to IEC 61000-6-4 Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4 Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 Conducted and radiated emissions class B group 1 conforming to CISPR 11 Conducted and radiated emissions class B conforming to CISPR 22
Standards
IEC 60255-1
product certifications
GL RCM CCC CSA UL EAC CE
Ambient air temperature for storage
-40…70 °C
Relative humidity
93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance
0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance
15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protection
IP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529
Pollution degree
3 conforming to IEC 60664-1
Dielectric test voltage
2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.6 cm
Package 1 Width
8.2 cm
Package 1 Length
9.5 cm
Package 1 Weight
109.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
40
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
4.999 kg
Unit Type of Package 3
P06
Number of Units in Package 3
640
Package 3 Height
75.0 cm
Package 3 Width
60.0 cm
Package 3 Length
80.0 cm
Package 3 Weight
88.484 kg
Warranty
18 months
Datasheet