Trade Price
POA
Per
1
Unit
Pack Quantity
This Acti9 C60H-DC is a low voltage direct current miniature circuit breaker (MCB). It has 1P, rated current 32A and C tripping curve. The rated short circuit breaking capacity goes up to 10kA at 220VDC conforming to EN 60947-2 standard and 10kA at 220VDC conforming to EN 60947-2 standard. This product complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuit against short circuit and overload current. It offers VisiTrip for safety during maintenance and VisiSafe to reduce intervention time. The Acti9 C60H-DC is used in direct current circuit (industrial control and automation, transport, renewable energy). This device is dedicated to industrial control, automations, transport and renewable energy applications. It has an electrical endurance going up to 3000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 250VDC. The Ui rated insulation voltage is 500VDC. The Uimp rated impulse withstand voltage is 6kV. The operating frequency is 50Hz or 60Hz. It is DIN rail mountable. Its width is 2 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The weight is 0.128kg. According to IEC 60529 standard, the degree of protection is IP20 and IP40 in enclosure. The operating temperature is -25°C to 70°C. The storage temperature is -40°C to 85°C.
Range
Acti9
Product name
Acti9 C60H-DC
Product or component type
Miniature circuit-breaker
Device short name
C60H-DC
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
32 A at 25 °C
Network type
DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
10 kA Icu at 220 V DC conforming to EN 60947-2 10 kA Icu at 220 V DC conforming to IEC 60947-2 6 kA Icu at 250 V DC conforming to EN 60947-2 6 kA Icu at 250 V DC conforming to IEC 60947-2 20 kA Icu at 110 V DC conforming to EN 60947-2 20 kA Icu at 110 V DC conforming to IEC 60947-2
Utilisation category
Category A conforming to EN 60947-2 Category A conforming to IEC 60947-2
Suitability for isolation
Yes conforming to IEC 60947-2 Yes conforming to EN 60947-2
Network frequency
50/60 Hz
[Ue] rated operational voltage
250 V DC
[Ics] rated service breaking capacity
15 kA 75 % conforming to EN 60947-2 - 110 V DC 15 kA 75 % conforming to IEC 60947-2 - 110 V DC 4.5 kA 75 % conforming to EN 60947-2 - 250 V DC 4.5 kA 75 % conforming to IEC 60947-2 - 250 V DC 7.5 kA 75 % conforming to EN 60947-2 - 220 V DC 7.5 kA 75 % conforming to IEC 60947-2 - 220 V DC
[Ui] rated insulation voltage
500 V DC conforming to IEC 60947-2 500 V DC conforming to EN 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2
Contact position indicator
Yes
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Fixed
mounting support
35 mm symmetrical DIN rail
Comb busbar and distribution block compatibility
Top or bottom: standard
9 mm pitches
2
Net weight
0.128 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
3000 cycles L/R = 2 ms
Provision for padlocking
Padlockable
Locking options description
In position O
Tightening torque
Power circuit: 2.5 N.m top or bottom
earth-leakage protection
Without
Standards
EN 60947-2 IEC 60947-2
Pollution degree
3 conforming to EN 60947-2 3 conforming to IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-2
Operating altitude
2000 m
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
7.0 cm
Package 1 Width
1.8 cm
Package 1 Length
7.5 cm
Package 1 Weight
121.0 g
Warranty
18 months