Trade Price
POA
Per
1
Unit
Pack Quantity
Range
MasterPacT
Product name
MasterPact NW DC
circuit breaker name
MasterPact NW10HDC-E
Product or component type
Circuit breaker
Device application
DC voltage switching
Poles description
4P
Control unit
Without control unit
[In] rated current
1000 A at 40 °C
Performance type
H 85 kA 500 V DC
[Ue] rated operational voltage
500/900 V DC
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Selectivity category
Category B
Control type
Push-button
Mounting mode
Fixed
[Icu] rated ultimate short-circuit breaking capacity
100 kA Icu at 500 V DC L/R = 5 ms 25 kA Icu at 900 V DC L/R = 30 ms 35 kA Icu at 900 V DC L/R = 15 ms 50 kA Icu at 500 V DC L/R = 30 ms 50 kA Icu at 750 V DC L/R = 15 ms 50 kA Icu at 750 V DC L/R = 30 ms 85 kA Icu at 500 V DC L/R = 15 ms 85 kA Icu at 750 V DC L/R = 5 ms 85 kA Icu at 900 V DC L/R = 5 ms
[Ics] rated service breaking capacity
100 kA at 500 V DC (L/R = 5 ms) 25 kA at 900 V DC (L/R = 30 ms) 35 kA at 900 V DC (L/R = 15 ms) 50 kA at 500 V DC (L/R = 30 ms) 50 kA at 750 V DC (L/R = 15 ms) 50 kA at 750 V DC (L/R = 30 ms) 85 kA at 500 V DC (L/R = 15 ms) 85 kA at 750 V DC (L/R = 5 ms) 85 kA at 900 V DC (L/R = 5 ms)
[Icw] rated short-time withstand current
85 kA 1 s
[Icm] rated short-circuit making capacity
100 kA L/R = 5 ms 500 V DC 25 kA L/R = 30 ms 900 V DC 35 kA L/R = 15 ms 900 V DC 50 kA L/R = 30 ms 500 V DC 50 kA L/R = 15 ms 750 V DC 50 kA L/R = 30 ms 750 V DC 85 kA L/R = 15 ms 500 V DC 85 kA L/R = 5 ms 750 V DC 85 kA L/R = 5 ms 900 V DC
Sensor rating
1000 A
[Ui] rated insulation voltage
1000 V DC
[Uimp] rated impulse withstand voltage
12 kV
Power dissipation in W
1000 W
Maximum breaking time
30…75 ms
maximum closing response time
70 ms
mounting support
Backplate Rails
Upside connection
Rear
downside connection
Rear
Connection pitch
115 mm
Mechanical durability
10000 cycles without maintenance conforming to IEC 60947-2 20000 cycles with maintenance conforming to IEC 60947-2
Electrical durability
8500 cycles 500 V DC without maintenance conforming to IEC 60947-2 2000 cycles 900 V DC without maintenance conforming to IEC 60947-2
height
352 mm
Width
537 mm
Depth
427 mm
Net weight
85…106 kg
standards
IEC 60947-2
product certifications
ASTA ASEFA
Pollution degree
4 conforming to IEC 60664-1
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Operating altitude
0...2000 m without derating 2000 m...5000 m with derating
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
0.1 cm
Package 1 Width
0.1 cm
Package 1 Length
0.2 cm
Package 1 Weight
93.734 kg
Warranty
18 months