48499

TRIP UNIT MICROLOGIC 5.0 E FOR MASTERPAC

Trade Price

£1,859.82

Per

1

Unit

EA

Pack Quantity

1

48499

Information

Micrologic 5.0E (Energy meter) is an electronic control unit used on Masterpact NW 08 to 63 drawout circuit breakers. This control unit has a selective protection (LSI) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. Micrologic 5.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 5.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with drawout Masterpact NW basic frame.

Technical Specifications

Range

MasterPact

Range of product

MasterPact NW

Product or component type

Control unit

Trip unit name

MicroLogic 5.0 E

Trip unit technology

Electronic

Range compatibility

Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection

Device application

Distribution

Number of poles

4P 3P

Protected poles description

4t 3t 3t + N/2

Trip unit protection functions

Selective protection

Protection type

for short time short-circuit protection for overload protection (long time) for instantaneous short-circuit protection

Trip unit rating

800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C

Network type

AC

Network frequency

50/60 Hz

Circuit breaker mounting mode

Drawout

Long-time pick-up adjustment type Ir (thermal protection)

Adjustable 9 settings

[Ir] long-time protection pick-up adjustment range

0.4...1 x In

Long-time protection delay adjustment type tr

Adjustable 9 settings

[tr] long-time protection delay adjustment range

0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir

Thermal memory

20 mn

Short-time protection pick-up adjustment type Isd

Adjustable 9 settings

[Isd] Short-time protection pick-up adjustment range

1.5...10 x Ir

Short-time protection delay adjustment type tsd

Adjustable

[tsd] Short-time protection delay adjustment range

0…0.4 s I²t=off 0.1…0.4 s I²t=on

Instantaneous protection pick-up adjustment type Ii

Adjustable 9 settings

[Ii] instantaneous protection pick-up adjustment range

2...15 x In Off

earth-leakage protection

Without

Zone selective interlocking ZSI

With

Local signalling

3 LEDs (red) for electrical fault 1 LED (red) for internal error

Display type

Digital display

Type of measurement

Energy meter

communication of data

Measurement readout Protection and alarm settings

Ambient air temperature for operation

-25…70 °C

Ambient air temperature for storage

-40…85 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

14.800 cm

Package 1 Width

14.800 cm

Package 1 Length

39.700 cm

Package 1 Weight

650.000 g

Unit Type of Package 2

P12

Number of Units in Package 2

32

Package 2 Height

45.000 cm

Package 2 Width

80.000 cm

Package 2 Length

120.000 cm

Package 2 Weight

39.200 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet