Trade Price
£1,353.32
Per
1
Unit
EA
Pack Quantity
1
Micrologic 2.0E (Energy meter) is an electronic control unit used on Masterpact NW 08 to 63 drawout circuit breakers. This control unit has a basic protection (LI) and is designed to protect power circuits and loads. It embeds adjustable long time protection against overloads. It provides also adjustable instantaneous protection against short-circuits. Micrologic 2.0E indicates overloads with an Alarm LED. It is able to display the trip cause through 3 others LEDs. Micrologic 2.0E is equipped with a digital LCD screen that displays the active energy with 2% accuracy. This control unit can be associated with drawout Masterpact NW basic frame.
Range
MasterPact
Range of product
MasterPact NW
Product or component type
Control unit
Trip unit name
MicroLogic 2.0 E
Trip unit technology
Electronic
Range compatibility
Masterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection
Device application
Distribution
Number of poles
4P 3P
Protected poles description
4t 3t 3t + N/2
Trip unit protection functions
Basic protection
Protection type
for overload protection (long time) for instantaneous short-circuit protection
Trip unit rating
800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Network type
AC
Network frequency
50/60 Hz
Circuit breaker mounting mode
Drawout
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
0.4...1 x In
Long-time protection delay adjustment type tr
Adjustable 9 settings
[tr] long-time protection delay adjustment range
0.7…16.6 s at 7.2 x Ir 0.7…24 s at 6 x Ir 12.5…600 s at 1.5 x Ir
Thermal memory
20 mn
Instantaneous protection pick-up adjustment type Ii
Adjustable 9 settings
[Ii] instantaneous protection pick-up adjustment range
1.5...10 x Ir
earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Local signalling
3 LEDs (red) for electrical fault 1 LED (red) for internal error
Display type
Digital display
Type of measurement
Energy meter
communication of data
Measurement readout Protection and alarm settings
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.8 cm
Package 1 Width
8.0 cm
Package 1 Length
21.5 cm
Package 1 Weight
366.0 g
Warranty
18 months
Datasheet