PCSPCTFCL200018

CT 2000 1 SPLIT RND 8ID

Trade Price

£2,821.21

Per

1

Unit

EA

Pack Quantity

1

PCSPCTFCL200018

Information

This round split-core current transformer, desinged to be opened with a twist motion, has a line rated current of 2000A and a secondary rating of 1A. The inner diameter of this coil is 203.2mm. Measurement accuracy of the primary rating is 4% from 200A to 300A, 3% from 400A to 500A, then 2% from 600A to 800A and 1% above. A flying lead of 3.65 meters with spade connectors is available at the secondary of the transformer. This product received the cURus certification, and CE.

Technical Specifications

Range

AccuSine

Product or component type

Current transformer

accessory / separate part category

Measurement accessory

Range compatibility

AccuSine (AccuSine PCS+) active harmonic filter AccuSine (AccuSine PFV+) electronic VAR controller

current transformer type

Split core

Shape

Round

Secondary current

1 A

current transformer ratio

2000/1

Electrical connection

Flying lead: 3.65 m720 V

Input impedance

18 Ohm

[In] rated current

2000 A

thermal factor

1.25 at 30 °C 1 at 55 °C

Network frequency

50...400 Hz

Measurement accuracy

1 %

Accuracy class

Class 1

[Ue] rated operational voltage

< 720 V AC 50...400 Hz

[Uimp] rated impulse withstand voltage

10 kV (50 µs)

Depth

38.1 mm outside:

Diameter

203.2 mm inner: 266.7 mm outer:

Net weight

2.5 kg

standards

IEC 60044-1

product certifications

CE cURus

Ambient air temperature for operation

-45…55 °C

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

10.2 cm

Package 1 Width

45.8 cm

Package 1 Length

45.8 cm

Package 1 Weight

2.495 kg

Warranty

18 months

Document Links

Datasheet