KTB0630DC4

630A plug in tap off unit

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

KTB0630DC4

Technical Specifications

Range of product

Canalis

Range compatibility

Canalis (KT) busbar trunking

Product or component type

Tap-off unit

busbar trunking compatibility

Canalis KT busbar trunking with KS type plug-in

[Ie] rated operational current

400…630 A at 35 °C

Protection type

Circuit breaker: NSX630

Provided equipment

circuit-breaker to be ordered separately

Mounting mode

Plug-in with auto-clamping system

Tap-off unit polarity

3L+N+PE

Device application

High power distribution

[Ue] rated operational voltage

500 V

[Uimp] rated impulse withstand voltage

8 kV

[Ui] rated insulation voltage

500 V

Network frequency

50/60 Hz

Control type

Rotary handle

Electrical connection

Cable clamp terminal - ISO70 300 mm² (x2) - for L/N Cable clamp terminal - ISO70 150 mm² (x1) - for PE

door/cover opening side

Front

Tap-off unit disconnection mode

By drawing out

Standards

IEC 61439-1 IEC 61439-6

Colour

White (RAL 9001)

Width

838 mm

Depth

520 mm

height

550 mm

Net weight

45 kg

Earthing system

TT TN-S IT

IP degree of protection

IP55 conforming to IEC 60529

IK degree of protection

IK08 conforming to IEC 62262

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

52 cm

Package 1 Width

55 cm

Package 1 Length

84 cm

Package 1 Weight

45 kg

Warranty

18 months

Document Links

Datasheet