KRC4000ER59

KR 5X4000CU CABLE END FEED UNIT

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

KRC4000ER59

Technical Specifications

Range

Canalis

Product name

KR

Product or component type

Cable end feeder trunking

Device short name

KRC

Product specific application

Enterprise data centres Oil and gas Healthcare Real estate and office buildings Mining minerals and metals Water and waste water

Device application

Feeder length

Supply

Oil-immersed transformer Switchboard

Material

Copper

[Ie] rated operational current

4000 A at 35 °C

busbar/connection pads direction type

Edgewise to straight

earth conductor

Standard earth

short-circuit level

Standard version

Housing material

Mineral epoxy resin

Contacts material

Copper

[Ue] rated operational voltage

1000 V

Network frequency

50/60 Hz

[Ui] rated insulation voltage

1000 V

[Icw] rated short-time withstand current

100 kA

[Ipk] rated peak withstand current

220 kA

Radiated magnetic field

37.09 mT

Thermal stress limit

10000000 kA².s

Maximum voltage drop

<0.002 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.003 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.003 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.003 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Mounting location

Outdoor Indoor

busbar incoming

Vertical

polarity

3L + N + PE

product certifications

CE ATEX EAC

standards

IEC 61439-6

Dimension type

Fix

Connection pitch

100 mm

Colour

Grey (RAL 7030)

Linear load

172 kg/m

IP degree of protection

IP68 conforming to IEC 60529

IK degree of protection

IK10 conforming to IEC 62262

Pollution degree

3

Fire resistance

760 °C 180 min conforming to IEC 60331-1

derating factor

0…35 °C (100 % of In) 35…40 °C (96 % of In) 40…45 °C (89 % of In) 45…50 °C (84 % of In) 50…55 °C (78 % of In)

Operating altitude

1000 m 100 % of In (indoor) 2000 m 99 % of In (indoor) 3000 m 96 % of In (indoor) 4000 m 90 % of In (indoor) 1000 m 98 % of In (outdoor) 2000 m 94 % of In (outdoor) 3000 m 89 % of In (outdoor) 4000 m 83 % of In (outdoor)

Environmental characteristic

EMC directive conforming to IEC 61439-6

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

80.0 cm

Package 1 Width

90.0 cm

Package 1 Length

62.0 cm

Package 1 Weight

180.6 kg

Warranty

18 months

Document Links

Datasheet