Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Range
Canalis
Product name
KR
Product or component type
Zed elbow
Device short name
KRC
Product specific application
Water and waste water Enterprise data centres Mining minerals and metals Healthcare Real estate and office buildings Oil and gas
Device application
Change direction
Material
Copper
[Ie] rated operational current
1600 A at 35 °C
polarity
3L + N + PE
earth conductor
Standard earth
short-circuit level
Standard version
Housing material
Mineral epoxy resin
Contacts material
Copper
[Ue] rated operational voltage
1000 V
Network frequency
50/60 Hz
[Ui] rated insulation voltage
1000 V
[Icw] rated short-time withstand current
65 kA
[Ipk] rated peak withstand current
140 kA
Radiated magnetic field
14.68 mT
Thermal stress limit
4225000 kA².s
Maximum voltage drop
<0.007 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.01 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.01 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.011 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Linear resistance
L: X1 35 °C= 0.046 mΩ/m at Inc and 50 Hz L-N: X0 20 °C= 0.116 mΩ/m symmetrical components method L: R20 20 °C= 0.031 mΩ/m L: R1 35 °C= 0.04 mΩ/m at Inc and 50 Hz L: Z1 35 °C= 0.061 mΩ/m at Inc and 50 Hz L - PE: R0 20 °C= 0.116 mΩ/m symmetrical components method L - PE: X0 20 °C= 0.139 mΩ/m symmetrical components method L - PE: Z0 20 °C= 0.182 mΩ/m symmetrical components method L-N: R0 20 °C= 0.075 mΩ/m symmetrical components method L-N: Z0 20 °C= 0.138 mΩ/m symmetrical components method
Mounting location
Outdoor Indoor
product certifications
EAC CE ATEX
standards
IEC 61439-6
Width
120 mm
Height
130 mm
Colour
Grey (RAL 7030)
Length
direction 1: 300…700 mm direction 2: 1…700 mm direction 3: 300…700 mm
Linear load
59 kg/m
IP degree of protection
IP68 conforming to IEC 60529
IK degree of protection
IK10 conforming to IEC 62262
Pollution degree
3
Fire resistance
760 °C 180 min conforming to IEC 60331-1
derating factor
0…35 °C (100 % of In) 35…40 °C (96 % of In) 40…45 °C (89 % of In) 45…50 °C (84 % of In) 50…55 °C (78 % of In)
Operating altitude
1000 m 100 % of In (indoor) 2000 m 99 % of In (indoor) 3000 m 96 % of In (indoor) 4000 m 90 % of In (indoor) 1000 m 98 % of In (outdoor) 2000 m 94 % of In (outdoor) 3000 m 89 % of In (outdoor) 4000 m 83 % of In (outdoor)
Environmental characteristic
EMC directive conforming to IEC 61439-6
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
39.0 cm
Package 1 Width
40.0 cm
Package 1 Length
40.0 cm
Package 1 Weight
74.34 kg
Warranty
18 months
Datasheet