Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Range
Canalis
Product name
KT
Product or component type
Busbar trunking
Busbar description
Neutral permutation length
Device short name
KTC
Device application
Feeder length
Material
Copper
[Ie] rated operational current
5000 A at 35 °C
polarity
3L + N + PE
Number of tap-off outlets
0
Length
1000 mm
provided equipment
Jointing unit Trunking unit
Housing material
Polyester film
Contacts material
Copper
[Ue] rated operational voltage
1000 V
Network frequency
50/60 Hz
[Ui] rated insulation voltage
1000 V
[Icw] rated short-time withstand current
95 kA
[Ipk] rated peak withstand current
209 kA
Radiated magnetic field
3 µT
Thermal stress limit
9025000 kA².s
THDI
33…100 % 3200 A 15…33 % 4000 A 0…15 % 5000 A
Maximum voltage drop
<0.0008 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.001 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.001 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.001 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Mounting mode
By hook
mounting support
Cantilever arm Pendant
Installation direction
Vertical Horizontal
Marking
Left side: L1 L2 L3 N Right side: N L1 L2 L3
earth conductor
Standard earth
short-circuit level
Standard version
Standards
IEC 61439-6 IEC 61439-1
Dimension type
Fix
Width
140 mm
height
404 mm
Colour
White (RAL 9001)
Linear load
114 kg/m
IP degree of protection
IP55 conforming to IEC 60529
IK degree of protection
IK08 conforming to IEC 62262
derating factor
0…35 °C (100 % of In) 35…40 °C (95 % of In) 40…45 °C (90 % of In) 45…50 °C (84 % of In) 50…55 °C (79 % of In)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
42.8 cm
Package 1 Width
14.0 cm
Package 1 Length
100.0 cm
Package 1 Weight
102.0 kg
Warranty
18 months
Datasheet