KSB160DM4

TOU 160A COMPACT NSXm

Trade Price

£1,026.60

Per

1

Unit

EA

Pack Quantity

1

KSB160DM4

Technical Specifications

Range of product

Canalis

Range compatibility

Canalis KS busbar trunking Canalis KT busbar trunking

Offer type

Classic

Product or component type

Tap-off unit

[Ie] rated operational current

160 A at 35 °C

Protection type

Circuit breaker: NSXm

Provided equipment

circuit-breaker to be ordered separately

Mounting mode

Plate with fixed polarity

Tap-off unit polarity

3L+N+PE

Colour

White (RAL 9001)

Device application

Medium power distribution

[Ue] rated operational voltage

400 V depending on protective device 500 V depending on protective device

[Uimp] rated impulse withstand voltage

6.8 kV

[Ui] rated insulation voltage

400 V depending on protective device 500 V depending on protective device

Network frequency

50/60 Hz

Control type

Extended rotary handle

Electrical connection

Crimp lug - ISO32 70 mm² flexible Crimp lug - ISO32 70 mm² rigid

door/cover opening side

Right

Tap-off unit disconnection mode

By rotary operating handle

Number of openings

1 opening for FL21 gland plate

Standards

IEC 61439-1 IEC 61439-6

Width

450 mm

Depth

251 mm

depth (door open)

675.5 mm

height

305 mm

Net weight

9.5 kg

Earthing system

TT TN-S IT

IP degree of protection

IP55 conforming to IEC 60529

IK degree of protection

IK08 conforming to IEC 62262

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

34.0 cm

Package 1 Width

37.0 cm

Package 1 Length

52.0 cm

Package 1 Weight

11.14 kg

Unit Type of Package 2

P06

Number of Units in Package 2

4

Package 2 Height

105.0 cm

Package 2 Width

60.0 cm

Package 2 Length

80.0 cm

Package 2 Weight

50.0 kg

Warranty

18 months

Document Links

Datasheet