KSA250EV4254

RISER DISTRIBUTION LENGTH 2.5M 4O

Trade Price

£749.20

Per

1

Unit

EA

Pack Quantity

1

KSA250EV4254

Information

Canalis busbar trunking for KSA. It's applied to rise medium power distribution with lubricated sliding contact. The operational voltage is from 230VAC 50/60Hz to 690VAC 50/60Hz. The rated operational current is 250A at 35 ℃. Mounted by screws with right neutral position. Rising main busbar whose material is aluminium and trunking polarity is 3L + N + PE. Designed with 4 tap-off outlets. It provides 0.69 µT radiated magnetic field. It is compliant with both IEC 60439-2 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).

Technical Specifications

Range

Canalis

Device short name

KSA

Offer type

Rising main

Product or component type

Busbar trunking

Busbar description

Vertical distribution length

Product compatibility

Canalis KSA busbar trunking 100…250 A

Conductors material

Aluminium

busbar trunking polarity

3L + N + PE

Number of tap-off outlets

4

[Ie] rated operational current

250 A at 35 °C

IP degree of protection

IP55 conforming to IEC 60529

Mounting mode

By screws

Dimension type

Fix

Length

2.5 m

Colour

White (RAL 9001)

Number of poles

4

Neutral position

Right

Mounting position

Vertical

[Ue] rated operational voltage

230...690 V

Network frequency

50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

[Ui] rated insulation voltage

690 V

[Icw] rated short-time withstand current

10 kA

[Ipk] rated peak withstand current

28 kA

Electrical connection

Lubricated sliding contact

Width

54 mm

height

146 mm

Net weight

12 kg

Tap-off unit interval

500 mm

Radiated magnetic field

0.69 µT

Thermal stress limit

100000 kA².s

THDI

0…15 % 250 A 15…33 % 200 A 33…100 % 160 A

Maximum voltage drop

<0.034 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.036 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.035 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.034 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Standards

IEC 61439-1 IEC 61439-6

IK degree of protection

IK08 conforming to IEC 62262

Ambient air temperature for operation

35 °C (without derating) 55 °C (with derating factor)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.4 cm

Package 1 Width

16.6 cm

Package 1 Length

258.8 cm

Package 1 Weight

18.35 kg

Unit Type of Package 2

PAL

Number of Units in Package 2

20

Package 2 Height

56.4 cm

Package 2 Width

68.0 cm

Package 2 Length

271.0 cm

Package 2 Weight

384.0 kg

Warranty

18 months