KSA250ED4081

RISER DISTRIBUTION LENGTH 0.8M 10

Trade Price

£925.59

Per

1

Unit

EA

Pack Quantity

1

KSA250ED4081

Information

Canalis busbar trunking for KSA. It's applied to rise medium power distribution with lubricated sliding contact. The operational voltage is from 230VAC 50/60Hz to 690VAC 50/60Hz. The rated operational current is 250A at 35 ℃. Mounted by screws with right neutral position. Riser foot busbar whose material is aluminium and trunking polarity is 3L + N + PE. Designed with 1 tap-off outlets. It provides 0.69 µT radiated magnetic field. It is compliant with both IEC 60439-2 and IEC 61439-6. It is also compliant with Green Premium (RoHS/REACH).

Technical Specifications

Range

Canalis

Device short name

KSA

Offer type

Rising main

Product or component type

Busbar trunking

Busbar description

Vertical distribution length

Product compatibility

Canalis KSA busbar trunking 100…250 A

Conductors material

Aluminium

busbar trunking polarity

3L + N + PE

Number of tap-off outlets

1

[Ie] rated operational current

250 A at 35 °C

IP degree of protection

IP55 conforming to IEC 60529

Mounting mode

By screws

Dimension type

Fix

Length

0.8 m

Colour

White (RAL 9001)

Number of poles

4

Neutral position

Right

Mounting position

Vertical

[Ue] rated operational voltage

230...690 V

Network frequency

50/60 Hz

[Uimp] rated impulse withstand voltage

8 kV

[Ui] rated insulation voltage

690 V

[Icw] rated short-time withstand current

10 kA

[Ipk] rated peak withstand current

28 kA

Electrical connection

Lubricated sliding contact

Width

54 mm

height

146 mm

Net weight

6.5 kg

Radiated magnetic field

0.69 µT

Thermal stress limit

100000 kA².s

THDI

0…15 % 250 A 15…33 % 200 A 33…100 % 160 A

Maximum voltage drop

<0.034 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.036 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.035 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.034 V with power factor = 0.7 at 50 Hz with 1A for 100 m long

Standards

IEC 61439-1 IEC 61439-6

IK degree of protection

IK08 conforming to IEC 62262

Ambient air temperature for operation

35 °C (without derating) 55 °C (with derating factor)

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.3 cm

Package 1 Width

16.6 cm

Package 1 Length

88.85 cm

Package 1 Weight

8.97 kg

Warranty

18 months

Document Links

Catalogue page

Datasheet