Trade Price
£400.52
Per
1
Unit
EA
Pack Quantity
1
Range
Canalis
Device short name
KSA
Offer type
Rising main
Product or component type
Busbar trunking
Busbar description
Vertical distribution length
Product compatibility
Canalis KSA busbar trunking 100…250 A
Conductors material
Aluminium
busbar trunking polarity
3L + N + PE
Number of tap-off outlets
3
[Ie] rated operational current
100 A at 35 °C
IP degree of protection
IP55 conforming to IEC 60529
Mounting mode
By screws
Dimension type
Fix
Length
2 m
Colour
White (RAL 9001)
Number of poles
4
Neutral position
Right
Mounting position
Vertical
[Ue] rated operational voltage
230...690 V
Network frequency
50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ui] rated insulation voltage
690 V
[Icw] rated short-time withstand current
2.6 kA
[Ipk] rated peak withstand current
15.7 kA
Electrical connection
Lubricated sliding contact
Width
54 mm
height
146 mm
Net weight
7 kg
Tap-off unit interval
500 mm
Radiated magnetic field
0.22 µT
Thermal stress limit
6800 kA².s
THDI
0…15 % 100 A 15…33 % 80 A 33…100 % 63 A
Maximum voltage drop
<0.138 V with power factor = 1 at 50 Hz with 1A for 100 m long <0.13 V with power factor = 0.9 at 50 Hz with 1A for 100 m long <0.118 V with power factor = 0.8 at 50 Hz with 1A for 100 m long <0.106 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Standards
IEC 61439-1 IEC 61439-6
IK degree of protection
IK08 conforming to IEC 62262
Ambient air temperature for operation
35 °C (without derating) 55 °C (with derating factor)
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
6.4 cm
Package 1 Width
16.6 cm
Package 1 Length
208.8 cm
Package 1 Weight
12.2 kg
Warranty
18 months
Datasheet