The PowerLogic P5 is Schneider Electric's withdrawable protection and control relay for demanding medium voltage distribution applications. This feeder relay offers withdrawable design with backup memory function enabling industry-leading 10 minute recovery time. It provides redundant Ethernet including IEC 61850 as well as plug and play communication modules that can evolve with your application. The product embeds latest cybersecurity functionality to help prevent intentional mis-use and cyber-threats. PowerLogic P5 offers safety, security, and connectivity built on more than 100 years of experience in protection relays. The PowerLogic P5 protection relay can be applied to all types of MV distribution networks. It can be supplied with 48 to 250 VDC and 100 to 230 VAC. It works with conventional CTs/VTs. 3 phase current inputs, 1 Schneider Electric specific CSH neutral current input and 4 voltage inputs. It offers 10 digital inputs and 8 digital outputs, Ethernet RSTP RJ45 module with Dual IP and backup memory module. The product dimensions are 180 mm in height (7.09 in), 152,4 mm in width (6.00 in) and 224 mm in depth 8.82 in) for a net weight of 3.5 kg (7.7 lbs). PowerLogic P5 is compliant with EN 60255-26, EN 60255-27 standard and with UL Standard. It provides Marine certification. This product can be flush mounted on the panel or in the rack. Flush mounting frames to ensure IP54 are available. Fixing and wiring accessories are included. Plug and play communication modules: Ethernet RSTP RJ45 (REL51038), Ethernet RSTP FO (REL51039), Ethernet HSR/PRP FO (REL51033). And also 2nd Ethernet RSTP RJ45 (REL51042), RS485 serial RJ45 (REL51036), RS485 serial FO (REL51040), Extension/backup memory (REL51034). IP54 flush mounting frame (REL51052), CSH core-balance CTs (59635, 59636, 59637), 8 temperature sensor module (59641), IRIG-B module (REL51045). connection cords (59660, 59661, 59662). eSetup Easergy Pro software with virtual injection testing and EcoStruxure Power Device app for simpler and safer operation and maintenance. Included with functions as per the datasheet below. For other configurations with additional functions and options, Please select via Product Selector.
Range of product
PowerLogic P5
Product or component type
Protection relay
Relay application
Feeder - directional over current
product reference
P5F30-AACB-HABAH-AAAA
Mounting case size
30TE
Device mounting
Flush
Mounting mode
Withdrawable
power supply
48...250 V DC 100...230 V AC
measuring inputs
: 1/5 A CT phase current 3 : CSH residual current 1 : VT voltage 4
number of Digital Inputs (DI)
10
number of Digital Outputs (DO)
7 DO 1 watchdog
number of analogue outputs
0
communication ports
RJ45 2 rear Extension port 1 rear with backup memory USB port 2 front
communication protocols
IEC 61850 ed. 1 IEC 61850 ed. 2 DNP3 over ethernet Modbus TCP EtherNet/IP
Redundancy communication port protocol
RSTP
Cybersecurity
Password protection Port hardening Firmware signature Client IP address filter Secured communication with assciated tools
protection functions
Phase overcurrent 50/51 Directional phase overcurrent 67 Earth fault overcurrent 50N/51N Directional earth fault 67N Transient earth fault 67NI Neutral admittance 21YN Earth fault wattmetric 32N Capacitor bank unbalance 51C Broken conductor 46 I2/I1 Current unbalance 46 I2/I1 Cold load pick-up Switch ON to fault (SOTF) H2 detection H5 detection Breaker failure 50BF Directional active underpower 37P Fault locator 21FL Recloser 79 Negative sequence overcurrent 46 Overvoltage 59 Undervoltage 27 Earth fault overvoltage 59N Underfrequency 81/81N Rate of change of frequency 81R Synchro-check 25 Lockout relay 86 CT supervision 60 VT supervision 60 Programmable stages 99 Programmable logic Programmable curve
measurement functions
Current 3-phase Current zero sequence Current positive sequence Current negative sequence Current ratio of negative and positive Phasor diagram of currents or voltages Current 2nd, 15th harmonics with THD Voltage 3-phase Voltage residual Voltage zero sequence Voltage positive sequence Voltage negative sequence Frequency
control functions
Switchgear control and monitoring Programmable switchgear interlocking Local/remote control
controllable switchgear devices
6 controlled + 2 monitored objects
number of setting groups
4
monitoring functions
Trip circuit supervision 74 Circuit breaker monitoring Relay self-monitoring
logs and records
Event recording Disturbance recording Tripping context Relay maintenance
Switchgear diagnosis type
CT/VT supervision ANSI code: 60 Trip circuit supervision ANSI code: 74
Connections - terminals
Screw (digital input/output) Ring lugs (analog inputs and outputs)
Time synchronisation protocol
SNTP
Web server
Embedded HTTP server
Software name
EcoStruxure Power Device ESetup Easergy Pro: virtual simulation test
Display type
and colour LCD 480 x 272 pixels
Number of key
7 customizable
Local signalling
4 x LED 10 x LED tri-colour programmable
Height
176 mm
Width
152 mm
Depth
219 mm
Net weight
3.5 kg
Electromagnetic compatibility
Emission tests class A conforming to CISPR 11 Emission tests class A conforming to CISPR 22 Emission tests conforming to IACS E10 EMC immunity class 4 conforming to IEC 61000-4-2 EMC immunity class 4 conforming to ANSI C37.90.3 EMC immunity level 3 conforming to IEC 61000-4-3 EMC immunity conforming to ANSI C37.90.2 EMC immunity conforming to GOST 32137 EMC immunity conforming to GOST 30804.4.3 EMC immunity conforming to IACS E10 EMC immunity level 5 conforming to IEC 61000-4-8 EMC immunity level 5 conforming to IEC 61000-4-9 EMC immunity level 5 conforming to IEC 61000-4-10 EMC immunity level 3 conforming to IEC 61000-4-6 EMC immunity level 3 conforming to IEC 61000-4-18 EMC immunity conforming to ANSI C37.90.1 EMC immunity conforming to IEC 61000-4-12 EMC immunity conforming to GOST 30804.4.12 EMC immunity level 4 conforming to IEC 61000-4-16 EMC immunity level 4 conforming to IEC 61000-4-4 EMC immunity level 4 conforming to IEC 61000-4-5
Mechanical robustness
Vibrations (level: class 2) conforming to IEC 60255-21-1 Vibrations conforming to GOST 17516.1 Vibrations conforming to IACS E10 Shocks (level: class 2) conforming to IEC 60255-21-2 Earthquakes (level: class 2) conforming to IEC 60255-21-3
climatic withstand
Exposure to cold conforming to IEC 60068-2-1 Exposure to dry heat conforming to IEC 60068-2-2 Exposure to damp heat in service conforming to IEC 60068-2-78 Exposure to damp heat in service conforming to IEC 60068-2-30 Temperature variation conforming to IEC 60068-2-14 Salt mist conforming to IEC 60068-2-52 Influence of corrosion/gas test 2 conforming to IEC 60068-2-60 Influence of corrosion/gas test 4 conforming to IEC 60068-2-60 Influence of corrosion/gas test 2 conforming to IEC 60721-3-3 Influence of corrosion/gas test 4 conforming to IEC 60721-3-3
Ambient air temperature for operation
-40…85 °C ( 16 h ) -40…70 °C ( 96 h )
Relative humidity
0…93 % at 40 °C, without condensation, 56 days 93…95 % at 25…55 °C, 6 cycles, 12 + 12 hours
maximum operating altitude
2000 m
Protective treatment
Conformal coating conforming to IEC 60068-2-52:Kb/1 Conformal coating conforming to IEC 60068-2-60:Ke Conformal coating conforming to IEC 60721-3-3:3C2
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
30.0 cm
Package 1 Width
30.0 cm
Package 1 Length
35.0 cm
Package 1 Weight
4.5 kg
Warranty
Up to 10 years extended warranty (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)