LC1D50ABNE

Cont 50A 3P AC3 24-60VACDC coil

Trade Price

£241.37

Per

1

Unit

EA

Pack Quantity

1

LC1D50ABNE

Information

TeSys D contactor, 3 poles (3NO), for motor control applications up to 50A/690V AC-3/3e (22kW@400V). It provides a low consumption 24-60V AC/DC coil with electronic control, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys TeSys Deca

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load Motor control

utilisation category

AC-1 AC-3 AC-3e

Poles description

3P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current

80 A (at <60 °C) at <= 440 V AC-1 for power circuit 50 A (at <60 °C) at <= 440 V AC-3 for power circuit 50 A (at <60 °C) at <= 440 V AC-3e for power circuit

[Uc] control circuit voltage

24...60 V AC 50/60 Hz 24...60 V DC

Motor power kW

15 kW at 220...230 V AC 50 Hz (AC-3) 22 kW at 380...400 V AC 50 Hz (AC-3) 25 kW at 415 V AC 50 Hz (AC-3) 30 kW at 440 V AC 50 Hz (AC-3) 30 kW at 500 V AC 50 Hz (AC-3) 33 kW at 660...690 V AC 50 Hz (AC-3) 15 kW at 220...230 V AC 50 Hz (AC-3e) 22 kW at 380...400 V AC 50 Hz (AC-3e) 25 kW at 415 V AC 50 Hz (AC-3e) 30 kW at 440 V AC 50 Hz (AC-3e) 30 kW at 500 V AC 50 Hz (AC-3e) 33 kW at 660...690 V AC 50 Hz (AC-3e)

Motor power hp

3 hp at 115 V AC 60 Hz for 1 phase motors 7.5 hp at 230/240 V AC 60 Hz for 1 phase motors 15 hp at 200/208 V AC 60 Hz for 3 phases motors 15 hp at 230/240 V AC 60 Hz for 3 phases motors 40 hp at 460/480 V AC 60 Hz for 3 phases motors 40 hp at 575/600 V AC 60 Hz for 3 phases motors

Compatibility code

LC1D

Pole contact composition

3 NO

Protective cover

With

[Ith] conventional free air thermal current

80 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit

Irms rated making capacity

900 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1

Rated breaking capacity

900 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit 84 A 40 °C - 10 min for power circuit 208 A 40 °C - 1 min for power circuit 400 A 40 °C - 10 s for power circuit 810 A 40 °C - 1 s for power circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1 100 A gG at <= 690 V coordination type 1 for power circuit 100 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.5 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole

9.6 W AC-1 3.7 W AC-3 3.7 W AC-3e

[Ui] rated insulation voltage

Power circuit: 690 V conforming to IEC 60947-4-1 Signalling circuit: 690 V conforming to IEC 60947-1

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

6 Mcycles

Electrical durability

1.8 Mcycles 42 A AC-3 at Ue <= 440 V 0.5 Mcycles 80 A AC-1 at Ue <= 440 V 1.8 Mcycles 42 A AC-3e at Ue <= 440 V

Control circuit type

AC/DC at 50/60 Hz AC/DC electronic

Coil technology

Built-in bidirectional peak limiting

Control circuit voltage limits

<= 0.1 Uc (-40…70 °C):drop-out AC/DC 0.85...1.1 Uc (-40…60 °C):operational AC 0.8...1.1 Uc (-40…60 °C):operational DC 1...1.1 Uc (60…70 °C):operational AC/DC

Inrush power in VA

15 VA 50/60 Hz (at 20 °C)

Inrush power in W

16 W (at 20 °C)

Hold-in power consumption in VA

1 VA 50/60 Hz (at 20 °C)

Hold-in power consumption in W

0.7 W at 20 °C

Heat dissipation

0.7 W at 50/60 Hz

Operating time

55...65 ms closing 20...120 ms opening (date code >= 17221) 20...80 ms opening (date code >= 18011)

Maximum operating rate

3600 cyc/h 60 °C

Connections - terminals

Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable end Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable end Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable end Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable end Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid

Tightening torque

Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm Power circuit: 5 N.m - with screwdriver pozidriv No 2 Control circuit: 1.7 N.m - with screwdriver pozidriv No 2

Auxiliary contact composition

1 NO + 1 NC

Auxiliary contacts type

type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency

25...400 Hz

Minimum switching voltage

17 V for signalling circuit

Minimum switching current

5 mA for signalling circuit

Insulation resistance

> 10 MOhm for signalling circuit

Non-overlap time

1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact

mounting support

Rail Plate

Standards

EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC 60335-1

product certifications

CCC CSA EAC UL KC DNV-GL LROS (Lloyds register of shipping) UKCA

IP degree of protection

IP20 front face conforming to IEC 60529

Climatic withstand

conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device

-40…60 °C 60…70 °C with derating

Operating altitude

0...3000 m

Fire resistance

850 °C conforming to IEC 60695-2-1

Flame retardance

V1 conforming to UL 94

Mechanical robustness

Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor open (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms)

height

122 mm

Width

55 mm

Depth

120 mm

Net weight

0.997 kg

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

6.2 cm

Package 1 Width

13.7 cm

Package 1 Length

15.2 cm

Package 1 Weight

1.045 kg

Unit Type of Package 2

S02

Number of Units in Package 2

9

Package 2 Height

15.0 cm

Package 2 Width

30.0 cm

Package 2 Length

40.0 cm

Package 2 Weight

9.722 kg

Warranty

18 months

Document Links

Datasheet