GV3L80

GV3L CB MAGNETIC 80A ELINK

Trade Price

£360.54

Per

1

Unit

EA

Pack Quantity

1

GV3L80

Information

TeSys GV motor circuit breaker, 3 poles (3P), 80A/690V, for 3-phase motor applications 45kW@400V. It provides a magnetic protection with a tripping level at 14xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary handle guaranteed for 20 000 cycles AC-3. To complete motor protection, use it in association with a thermal overload relay LRD380 (to be ordered separately). Multi standards certified (IEC, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Technical Specifications

Range

TeSys Deca

Product name

TeSys GV3 TeSys Deca

Product or component type

Motor circuit breaker

Device short name

GV3L

Device application

Motor protection

Trip unit technology

Magnetic

Poles description

3P

Network type

AC

Utilisation category

Category A conforming to IEC 60947-2

Network frequency

50/60 Hz

Fixing mode

35 mm symmetrical DIN rail: clipped Panel: screwed (with 3 x M4 screws)

Motor power kW

45 kW at 400/415 V AC 50/60 Hz maximum peak current 750 A 45 kW at 500 V AC 50/60 Hz maximum peak current 750 A 55 kW at 690 V AC 50/60 Hz maximum peak current 750 A

Breaking capacity

65 kA Icu at 230/240 V AC 50/60 Hz 50 kA Icu at 400/415 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz

[Ics] rated service short-circuit breaking capacity

100 % at 230/240 V AC 50/60 Hz 60 % at 400/415 V AC 50/60 Hz 60 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz

Control type

Rotary handle

[In] rated current

80 A

Magnetic tripping current

1120 A

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Suitability for isolation

Yes conforming to IEC 60947-1

Power dissipation per pole

8 W

Mechanical durability

50000 cycles

Electrical durability

20000 cycles for AC-3 at 415 V In

Tightening torque

5 N.m - on screw clamp terminal

Width

55 mm

height

132 mm

Depth

136 mm

Net weight

0.96 kg

Colour

Dark grey

standards

EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1

product certifications

CCC CSA EAC LROS (Lloyds register of shipping) BV ABS DNV-GL UKCA

IP degree of protection

IP20 conforming to IEC 60529

Climatic withstand

conforming to IACS E10

Ambient air temperature for storage

-40…80 °C

Fire resistance

960 °C conforming to IEC 60695-2-11

Ambient air temperature for operation

-20…60 °C

Mechanical robustness

Shocks: 5 Gn for 11 ms contactor open Shocks: 30 Gn for 11 ms contactor closed Vibrations: 4 Gn, 5...300 Hz

Operating altitude

3000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

15.800 cm

Package 1 Width

6.500 cm

Package 1 Length

14.600 cm

Package 1 Weight

1.334 kg

Unit Type of Package 2

S02

Number of Units in Package 2

8

Package 2 Height

15.000 cm

Package 2 Width

30.000 cm

Package 2 Length

40.000 cm

Package 2 Weight

8.414 kg

Unit Type of Package 3

P06

Number of Units in Package 3

120

Package 3 Height

73.500 cm

Package 3 Width

80.000 cm

Package 3 Length

60.000 cm

Package 3 Weight

136.720 kg

Warranty

18 months

Document Links

Datasheet