Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1
Range
TeSys
Range of product
TeSys Deca
Product or component type
Contactor
Device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1 AC-3 AC-3e AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
230 V AC 50/60 Hz
Compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
80 A (at 60 °C) for power circuit
Irms rated making capacity
1000 A at 440 V AC for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
110 A 40 °C - 10 min for power circuit 260 A 40 °C - 1 min for power circuit 520 A 40 °C - 10 s for power circuit 900 A 40 °C - 1 s for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V UL certified Power circuit: 600 V CSA certified
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 80 A AC-1 at Ue <= 440 V
Control circuit type
AC at 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA
245 VA 50/60 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA
26 VA 50/60 Hz cos phi 0.3 (at 20 °C)
Heat dissipation
6…10 W at 50/60 Hz
Operating time
4...19 ms opening 12...26 ms closing
Maximum operating rate
3600 cyc/h 60 °C
Connections - terminals
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid Power circuit: screw connectors 1 2.5…25 mm² - cable stiffness: solid Power circuit: screw connectors 2 2.5…16 mm² - cable stiffness: solid Power circuit: screw connectors 1 2.5…25 mm² - cable stiffness: flexible with cable end Power circuit: screw connectors 2 2.5…10 mm² - cable stiffness: flexible with cable end Power circuit: screw connectors 1 2.5…25 mm² - cable stiffness: flexible without cable end Power circuit: screw connectors 2 2.5…16 mm² - cable stiffness: flexible without cable end
Tightening torque
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 to Ø 8 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition
Without
mounting support
Plate Rail
Standards
EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 EN 60335-1
product certifications
IEC UL CSA CCC UKCA
IP degree of protection
IP20 front face conforming to IEC 60529
Climatic withstand
conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40…60 °C 60…70 °C with derating
Operating altitude
0...3000 m
Fire resistance
850 °C conforming to IEC 60695-2-1
Flame retardance
V0 conforming to UL 94
Mechanical robustness
Shocks contactor open (8 Gn for 11 ms) Shocks contactor closed (10 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz)
height
127 mm
Width
85 mm
Depth
130 mm
Net weight
1.44 kg
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
14.8 cm
Package 1 Width
13.1 cm
Package 1 Length
10.8 cm
Package 1 Weight
2.5 kg
Warranty
18 months